SIRIUS 3RT2 contactors/contactor assemblies
2.8 Technical data
SIRIUS Innovations
236
System Manual, 01/2011, A8E56203870002-03
2.8.1.5
Main circuit - 3RT201. contactors (current carrying capacity for alternating current and
direct current)
Table 2- 81 Main circuit - Current carrying capacity for alternating current (3RT201. contactors)
Type
3RT2015
3RT2016
3RT2017
3RT2018
Size
S00
Main circuit - Current carrying capacity for alternating current
Utilization category AC-1, switching resistive loads
Rated operational current I
e
At 40 °C up to 690 V
A
18
22
At 60 °C up to 690 V
A
16
20
Rated powers of three-phase current loads
1)
cos ϕ = 0.95 (at
60 °C)
230 V
kW
6.3
7.5
400 V
kW
11
13
500 V
kW
13.8
17
690 V
kW
19
22
Minimum conductor cross-section for loads with I
e
At 40 °C
mm
2
2.5
At 60 °C
mm
2
2.5
Utilization category AC-2 and AC-3
Rated operational currents I
e
400 V
A
7
9
12
16
440 V
A
7
9
11
15
500 V
A
6
7.7
9.2
12.4
690 V
A
4.9
6.7
6.7
8.8
Rated powers of slip-ring or squirrel-cage motors at 50 Hz and
at 60 Hz
230 V
kW
2.2
3
3
4
400 V
kW
3
4
5.5
7.5
500 V
kW
3.5
4.5
5.5
7.5
690 V
kW
4
5.5
5.5
7.5
Thermal load
10 s current
2)
A
56
72
96
128
Power loss per current path
At I
e
/AC-3
W
0.42
0.7
1.24
2.2
Содержание SIRIUS 3RH Series
Страница 1: ...SIRIUS Innovations System Manual 01 2011 Industrial Controls Answers for industry ...
Страница 2: ......
Страница 640: ...SIRIUS 3RA21 22 load feeders 6 12 Circuit diagrams SIRIUS Innovations 640 System Manual 01 2011 A8E56203870002 03 ...
Страница 760: ...Appendix A A 3 Correction sheet SIRIUS Innovations 760 System Manual 01 2011 A8E56203870002 03 ...
Страница 785: ......