Connecting cable to the encoder
The maximum cable length depends on the specification for the encoder supply
and the baud rate. If you use pre-assembled SIEMENS connecting cables (see
Catalogs NC Z/NC 60/ST 70), problem-free operation can be guaranteed only if
the following values are not exceeded:
Table 3-9
Maximum cable lengths, depending on the encoder power supply
Supply voltage
Encoder supply
voltage range
Power con-
sumption
Max. cable length
5 VDC
4.75 V...5.25 V
< 300 mA
25 m
5 VDC
4.75 V...5.25 V
< 210 mA
35 m
24 VDC
20.4 V...28.8 V
< 300 mA
100 m
24 VDC
11 V...30 V
< 300 mA
250 m
Table 3-10
Maximum cable lengths, depending on the baud rate
Encoder type
Frequency
Max. cable length
1 MHz
10 m
Incremental encoder
500 kHz
35 m
1.5 Mbits/s
10 m
Absolute encoder (SSI)
187.5 Kbyte/s
250 m
Содержание SIMOTION C230-2
Страница 10: ...Table of Contents Contents 10 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 16: ...Product Overview 1 16 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 70: ...Installation 4 70 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 124: ...Commissioning 8 124 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 130: ...Maintenance 9 130 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 141: ...B 141 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition EC Declaration of Conformity B ...
Страница 144: ...EC Declaration of Conformity B 144 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...