Device Data
3-43
E
Siemens AG, 2003 All rights reserved
SIMOTION C230-2, 04.2003 Edition
Connector pin assignment
Designation:
X1
Type:
40-pin S7 front connector for single-wire connection
Table 3-11
Front connector X1 pin assignment
Pin
Name
Type
Pin
Name
Type
1
L+
VI
21
Unassigned
2
Q0
DO
22
BERO1
DI
3
Unassigned
23
BERO2
DI
4
Q1
DO
24
BERO3
DI
5
Unassigned
25
BERO4
DI
6
Q2
DO
26
MEPU1
DI
7
Unassigned
27
MEPU2
DI
8
Q3
DO
28
I0
DI
9
Unassigned
29
I1
DI
10
RDY.1
K
30
I2
DI
11
RDY.2
K
31
I3
DI
12
Unassigned
32
I4
DI
13
Q4
DO
33
I5
DI
14
Unassigned
34
I6
DI
15
Q5
DO
35
I7
DI
16
Unassigned
36
I8
DI
17
Q6
DO
37
I9
DI
18
Unassigned
38
I10
DI
19
Q7
DO
39
I11
DI
20
M
output
VI
40
M
input
VI
Signal names
RDY.1...2
Ready (READY contact 1...2)
BERO1...BERO4
BERO input for axes 1...4
MEPU1, MEPU2
Measuring pulse inputs 1 and 2
I0...I11
Digital inputs 0...11
Q0...Q7
Digital outputs 0...7
L+
Supply for digital outputs
M
output
Reference potential for digital outputs
M
input
Reference potential for digital inputs
Signal type
DI
Digital input (24 V signal)
DO
Digital output (24 V signal)
K
Switching contact
VI
Voltage input
Содержание SIMOTION C230-2
Страница 10: ...Table of Contents Contents 10 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 16: ...Product Overview 1 16 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 70: ...Installation 4 70 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 124: ...Commissioning 8 124 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 130: ...Maintenance 9 130 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...
Страница 141: ...B 141 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition EC Declaration of Conformity B ...
Страница 144: ...EC Declaration of Conformity B 144 E Siemens AG 2003 All rights reserved SIMOTION C230 2 04 2003 Edition ...