7 Drive Machine Data (SIMODRIVE Drive MD)
7.2.2 FDD MD (data description - SW 3)
Natural frequency current setpoint filter 4
1208
Default value
Lower input limit
Upper input limit
Units
0
0
8 000
Hz
Active
at once
Input of natural frequency for current setpoint filter 4 (PT2 low-pass). An entry of < 10 Hz as
the natural frequency of the low-pass filter initializes the filter as a proportional element with a
gain of 1 independently of the associated damping. The filter is activated via machine data MD
1200 and MD 1201.
Damping current setpoint filter 4
1209
Default value
Lower input limit
Upper input limit
Units
1.0
0.05
5
–
Active
at once
Input of damping for current setpoint filter 4 (PT2 low-pass). The filter is activated via machine
data MD 1200 (selection current setpoint filter) and MD (type current setpoint filter) 1201.
Block frequency current setpoint filter 1
1210
Default value
Lower input limit
Upper input limit
Units
3 500.0
1
7 999.0
Hz
Active
at once
Input of block frequency for current setpoint filter 1 (band-stop). When block frequencies of <
10 Hz are input, the filter is deactivated (proportional element with a gain of 1). The filter is
activated via machine data MD 1200 and MD 1201.
Note:
The maximum block frequency input value is limited by the sampling frequency of the control
(MD 1000) (parameterization error).
1
1
MD 1210 <
–––––––– = –––––––––
2 x MD 1000 2 x T
sampl.
MD 1000 = T
sampl.
=
62.5
µ
s
125.0
µ
s
=> MD 1210 <
8000 Hz
4000 Hz
©
Siemens AG 1992 All Rights Reserved 6FC5197- AA50
7–59
SINUMERIK 840C (IA)