Data Exchange with the SM 335
3-9
SM 335 – High-Speed Analog Input/Output Module for the SIMATIC S7-300
6ES7 335-7HG00-8BA1
Table 3-6
Analog Value Representation in the Unipolar Input Ranges
Measuring Range
Units
Range
0 – 2 V
0 –10 V
0 – 20 mA
4 – 20 mA
decimal
hexa-
decimal
2.370 V
:
:
11.852 V
:
:
23.70 mA
:
:
22.96 mA
:
:
32767
:
32512
7FFF
H
:
7F00
H
Overflow
2.35 V
:
:
11,75 V
:
:
23.5 mA
:
:
22.8 mA
:
:
32510
:
27650
7EFE
H
:
6C02
H
Overrange
2 V
:
1.5 V
:
144.68
µ
V
0 V
10 V
:
7.5 V
:
723.4
µ
V
0 V
20 mA
:
15 mA
:
1446.8 nA
0 mA
20 mA
:
15 mA
:
4 mA +
1157.4 nA
4 mA
27648
:
20736
:
2
0
6C00
H
:
5100
H
:
2
H
0
Rated range
–144,68
µ
V
:
–18.446 mV
–723,4
µ
V
:
–92.223 mV
1446.8 nA
:
18.448
µ
A
<4 mA
Open wire
(7FFF
H
)
–2
:
–255
FFFE
H
:
FF00
H
Underrange
<–18.446 mV
<–92.223 mV
<–18.448
µ
A
–32768
8000
H
Underflow