System overview
3.7 Communication
Automation system
70
System Manual, 12/2017, A5E03461182-AE
3.7.2
Communication modules/processors
For special requirements of your plant, use communications processors (CPs) for security
functions to secure Industrial Ethernet networks.
If your system requires additional interfaces, communication modules (CM) expand your S7-
1500 CPU with other interfaces of an interface type such as PROFINET, PROFIBUS or
point-to-point connection. The CMs for point-to-point connection allow, for example, Freeport
or Modbus communication via their RS232, RS422 and RS485 interfaces.
Communication modules for PROFINET and Industrial Ethernet
Short designation
CM 1542-1
CP 1543-1
Article number
Manual
Bus system
PROFINET
Industrial Ethernet
Interface
RJ45
RJ45
Data transmission rate
10/100 Mbps
10/100/1000 Mbps
Functionality and protocols
TCP/IP, ISO-on-TCP, UDP, Modbus
TCP, S7 communication,
IP Broadcast/Multicast, IP routing,
SNMPv1
TCP/IP, ISO, UDP, Modbus TCP, S7
communication,
IP Broadcast/Multicast, Security, Se-
cure Open User Communication,
SMTPS, diagnostics SNMPV1/V3,
DHCP, FTP client/server e-mail,
IPV4/IPV6
Diagnostic interrupt
X
X
Hardware interrupt
X
---
Isochronous mode
---
---
Communication modules for PROFIBUS
Short designation
CM 1542-5
CP 1542-5
Article number
Manual
Bus system
PROFIBUS
PROFIBUS
Interface
RS485
RS485
Data transmission rate
9600 bps to 12 Mbps
9600 bps to 12 Mbps
Functionality and protocols
DPV1 master/slave,
S7 communication,
PG/OP communication,
Open User Communication
DPV1 master/slave,
S7 communication,
PG/OP communication,
FDL
Diagnostic interrupt
X
X
Hardware interrupt
X
X
Isochronous mode
---
---