System overview
3.6 Input and output modules
Automation system
System Manual, 12/2017, A5E03461182-AE
63
3.6.4
Fail-safe digital modules
Fail-safe digital modules
Fail-safe digital modules are available for implementing safety concepts in the area of
equipment and personnel safety (for example, for emergency stop devices in the operation
of processing machines).
The fail-safe modules ensure safe processing of field information (sensors: e.g., emergency
stop buttons, light barriers; actuators, e.g. motor control). You are provided with all the
hardware and software components required for safe processing, according to the required
safety class. The following table shows the available fail-safe modules.
Short designation
F-DI 16x 24VDC PROFIsafe
F-DQ 8x24VDC/2A PPM
Article number
Manual
Width
35 mm
35 mm
Number of inputs
16
---
Number of outputs
---
8
Type output
---
Transistor
Electrical isolation between channels
---
---
Rated input voltage
24 V DC
---
Rated output voltage
---
24 V DC
Rated output current
---
2 A
Maximum achievable safety class in
safety mode
PLe/SIL 3
PLe/SIL 3
Low demand mode: PFD according to
SIL3
< 5.00E-05
< 6.00E-05
High demand/continuous mode: PFH
according to SIL3
< 1.00E-09 1/h
< 2.00E-09 1/h
Diagnostic interrupt
X
X
Hardware interrupt
---
---
Input delay
0.4 ms to 20 ms (configurable by chan-
nel)
---
Benefits
The fail-safe input and output modules S7-1500 provide you with the following advantages:
●
High-channel, fail-safe inputs and outputs
●
can be used centrally in SIMATIC S7-1500 and in ET 200MP distributed I/O system
●
processing of standard and safety programs
●
uniform engineering for standard and safety automation in the TIA Portal
●
Integration of safety functions up to SIL 3 according to IEC 62061 and PL e according to
EN ISO 13849-1