Installation
5.7 Installing I/O modules
Automation system
System Manual, 12/2017, A5E03461182-AE
121
Installing I/O modules
Watch video sequence (
http://www.automation.siemens.com/salesmaterial-as/interactive-
manuals/getting-started_simatic-s7-1500/videos/EN/mount/start.html
Proceed as follows to install an I/O module:
1.
Insert a U connector into the back right on the I/O module.
Exception: the last I/O module in the assembly
2.
Hook the I/O module on the mounting rail and slide the I/O module up to module on the
left.
3.
Pivot the I/O module towards the back.
4.
Tighten the screw for the I/O module (torque 1.5 Nm).
Figure 5-8
Installing I/O module
Uninstalling I/O modules
The I/O module is wired.
Proceed as follows to dismantle an I/O module:
1.
Turn off all feed supply voltages.
2.
Open the front cover.
3.
For communications modules: Loosen and remove the connector from the module.
At I/O modules: Pull the front connector out of the I/O module using the unlocking strap.
Swivel the front connector downward and remove it from the groves.
4.
Loosen the fixing screw of the I/O module.
5.
Pivot the I/O module out of the mounting rail.