8-46
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Technical Specifications
Address ID for ET 200U
S
DP Siemens
S
DP Standard
4AI or 015
2AI or 013
1AI or 012
4AI or 083
2AI or 081
1AI or 080
Input ranges
(rated value)
"
1 V
Number of inputs
1, 2 or 4
(selectable)
Galvanic isolation
yes (inputs to ground–
ing point; not between
inputs)
Input resistance
w
10 M
Connection method of sensors
two–wire connection
Digital representation of input
signal
12 bits + sign (2048
units = rated value)
Measured value representation
of input signal
two’s complement
(left–justified)
Measuring principle
integrating
Conversion principle
voltage–time conver-
sion (dual slope)
Integration time
(adjustable for optimum noise
suppression)
20 ms at 50 Hz
16.6 ms at 60 Hz
Encoding time per input
S
for 2048 units
S
for 4095 units
max. 60 ms at 50 Hz
max. 50 ms at 60 Hz
max. 80 ms at 50 Hz
max. 66.6 ms at 60 Hz
Permissible voltage difference
S
between inputs
S
between inputs and central
grounding point
max.
"
1 V
max. 75 V DC /
60 V AC
Permissible input voltage
(destruction limit)
max. 24 V DC
Fault indication for
S
range exceeded
S
sensor wire break
S
general indication of wire
break
yes
(more than 4095 units)
yes (selectable)
red LED
Noise suppression for f = nx
(50 / 60 Hz
"
1 %);
n = 1, 2, ...
S
common–mode rejection
S
(V
pp
= 1 V)
S
series–mode rejection(peak
value of noise < rated va-
lue of input range)
min 86 dB
min. 40 dB
Basic error limits
(operational error limit at
25
_
C, referred to input ranges
of module)
0.1 %
Operational error limits
(0 to 60
_
C, referred to input
ranges of module)
"
0.35 %
Single errors
S
linearity
S
tolerance
S
polarity reversal error
"
0.05 %
"
0.05 %
"
0.05 %
Temperature error
S
final value
S
zero point
"
0.01 %/K
"
0.002 %/K
Length of cable
S
shielded
max. 200 m (660 ft.)
Supply voltage L+
none
Temperature compensation, in-
ternally
possible
Connection of compensating
box
not possible
Rated isolation voltage
(+9 V to )
S
isolation group
S
tested with
12 V AC
1
B
500 V AC
Rated isolation voltage
(inputs to +9 V)
S
isolation group
S
tested with
60 V AC
1
B
500 V AC
Current consumption
S
from +9 V (CPU)
typ. 70 mA
Power loss of the module
typ. 0.7 W
Weight
approx. 230 g (8 oz.)
Module Spectrum