8-54
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Fault indication for
S
range exceeded
S
sensor wire break
S
general indication of wire
break
yes
(more than 4095 units)
yes (selectable)
red LED
Noise suppression for f = nx
(50 / 60 Hz
"
1 %);
n = 1, 2, ...
S
common–mode rejection
(V
pp
= 1 V)
S
series–mode rejection
S
(peak value of noise < ra-
ted value of input range)
min. 86 dB
min. 40 dB
Basic error limits
(operational error limit at
25
_
C, referred to input ranges
of module)
"
0.15 %
Operational error limits
(0 to 60
_
C, referred to input
ranges of module)
"
0.4 %
Single errors
S
linearity
S
tolerance
S
polarity reversal error
"
0.05 %
"
0.05 %
"
0.05 %
Temperature error
S
final value
S
zero point
"
0.01 %/K
"
0.002 %/K
Supply voltage L+
Auxiliary curent for PT 100
none
2.5 mA
Resistance sensor
S
tolerance
S
temperature error
S
load dependency
"
0.05 %
"
0.006 %/K
"
0.02 %/100
Rated isolation voltage
(+9 V to )
S
isolation group
S
tested with
12 V AC
1
B
500 V AC
Rated isolation voltage
(inputs to +9 V)
S
isolation group
S
tested with
60 V AC
1
B
500 V AC
Current consumption
S
from + 9 V (CPU)
typ. 70 mA
Power loss of the module
typ. 0.9 W
Weight
approx. 230 g (8 oz.)