AdvancedCmd and Ident profile
C.2 The "Ident profile" block
Communications module RF120C with application blocks for S7-1200 and S7-1500
88
Operating Instructions, 07/2013, C79000-G8976-C328-01
Table C- 2 Permitted settings for the "CMD" parameter
Parameter
Command
CMD_ID
LEN_DATA
ADR_TAG
ATTR
Write
71h
Length of the data
to be written
Address on the
transponder
-
Read
70h
Length of the data
to be read
Address on the
transponder
-
MEM-Status
73h
-
-
RF200: 83h
RF300: 82h, 83h
RF600: 84h, 85h
MOBY D: 83h
DEV-Status
74h
-
-
RF200: 81h
RF300: 81h, 86h
RF600: 87h, 88h, A0h,
A1h
1)
MOBY U: 81h, 84h
MOBY D: 81h
Inventory
69h
-
-
RF600: 82h, 83h, 85h,
90h, 91h, 92h, A0h, A1h
1)
Format
66h
Value: 15
The memory size
and the
initialization value
must be stored in
the data buffer
2)
-
-
1)
Details: See Function manual for RF620R/RF630R. There, the DEV status corresponds to the
"SLG-Status" command and Inventory corresponds to the "GET" command.
The attributes must be compiled as follows: 81h → 01h, 82h → 02h, 83h → 03h, 85h → 05h, 87h →
07h
, 90h → 10h, 91h → 11h, 92h → 12h, A0h → 20, A01 → 21
2)
Details: refer to the Function manual for the RFID standard profile
As an alternative, the settings possible with the "AdvancedCmd" function block can also be
made with the Ident profile (see section "The "Ident profile" block (Page 88)").
C.2
The "Ident profile" block
Note
Parallel operation using the FB and Ident profile is not possible
The RF120C communications module must not be operated using the function blocks and
the Ident profile at the same time.