Service and maintenance
5.3 FB error messages
Communications module RF120C with application blocks for S7-1200 and S7-1500
58
Operating Instructions, 07/2013, C79000-G8976-C328-01
Byte
Description
0
1
2
E6h FEh 04h
•
Presence error: A transponder has passed by a reader without being processed by a command.
•
This error message is not reported immediately. Instead, the communications module is waiting
for the next command (read, write). This command is immediately replied to with this error. This
means that a read or write command is not processed. The next command is executed normally
again by the communications module.
•
An init_run from the Ident profile also resets this error status.
•
Bit 2 is set in the OPT1 parameter and there is no transponder in the transmission window.
E6h FEh 05h An error has occurred that makes a Reset_Reader (WRITE-CONFIG with Config = 3) necessary.
•
Error(s) in the WRITE-CONFIG command
•
Start init_run command after error correction
•
Check the HW_CONNECT parameter.
E6h FEh 06h The timer for "Reset_Reader" has elapsed
E7h FEh 01h In this state, only the "Reset_Reader" command is permitted.
E7h FEh 02h The CMD command code is not permissible.
E7h FEh 03h The length parameter of the command is too long.
It does not match the global data reserved in the send data buffer (TXBUF).
E7h FEh 04h Overflow of the receive data buffer (RXBUF)
More data was received than memory available in the RXBUF
E7h FEh 05h This error tells the user that only an INIT command is permissible as the next command. All other
commands are rejected.
E7h FEh 06h Wrong index (outside range of 101 to 108)
E7h FEh 07h Communications module does not respond to INIT (INIT_ACTIVE is expected in the cyclic status
message).
E7h FEh 08h Time exceeded during INIT
(60 seconds according to TC3WG9)
E7h FEh 09h Command repetition is not supported.
Fxh FEh xxh An FxFExxh error is identical to the corresponding ExFExxh error (see ExFExxh).
Byte 3 contains additional warning information.