Mounting and connecting the Extension Unit
3.6 Installing Advanced operator controls
Extension Units KPxx
44
Operating Instructions, 05/2019, A5E43600360-AC
3.6
Installing Advanced operator controls
NOTICE
Use only approved operator controls
Operator controls that are not approved may damage the Extension Unit and the PRO
device. Only install operator controls with Siemens approval in the Extension Unit, see
section "Advanced installation components (Page 21)".
Do not confuse the Standard and Advanced installation components and emergency stop
button.
Ensure appropriate connection of plug and plug-in connector:
•
Do not try to connect the 5-pin hardwired connector of the wiring harness (emergency
stop) to the 6-pin connector of an operator control.
•
Do not try to connect the 6-pin connector of the wiring harness to the 5-pin connector of
the emergency stop.
•
Do not try to connect the 6-pin internal bus connector (Advanced operator controls) to
the 6-pin connector of a Standard operator control.
•
Do not try to connect the 6-pin connector of the wiring harness (Standard operator
controls) to the 6-pin connector of an Advanced operator control.
Procedure
1.
First, proceed as you would when installing a Standard operator control, steps 1 to 4.
2.
Plug the connection module of the Advanced operator control into the Extension Unit
Advanced so that for the two connectors:
–
The solder pins point to the right (see marking).
–
The connection is made to the left (see arrow).
Use screws to fasten the connection module at positions
①
with the enclosure of the
Extension Unit, torque 0.8 Nm.