10.Select the "PV_Out#Value" tag in the detail view.
11.Click "OK".
This accepts the variable and its entire path in the "Dynamic" column.
12.Double-click "100" in the "Static" column for the "Max" attribute.
The "Enter Value" dialog box opens.
13.Enter "600" in the "Max" input box and then click "OK".
This applies the value.
14.Apply the parameters for the minimum value.
15.Close the "Object Properties" dialog box.
16.Select File > Save to save the process picture.
Configuring the operator station
9.7 Creating the process picture
PCS 7 SMART Getting Started - Part 1 (V9.0 with APL)
166
Getting Started, 12/2017, A5E42181435-AA