Installing and putting a TIM into operation
5.5 Installing a TIM
SINAUT ST7 Station control system - System Manual
System Manual, 05/2007, C79000-G8976-C178-06
213
Permitted ambient temperature
The SINAUT ST7 components can be operated in the same temperature range specified for
the S7-300.
Table 5-42 Permitted ambient temperatures for the SINAUT TIM modules
Installation position
Permitted ambient temperature (operation)
TIM
Horizontally installed rack
0 to 60 °C
TIM
Vertically installed rack
0 to 40 °C
Dimensions for installing the SINAUT TIM modules
Table 5-43 Dimensions for installing the SINAUT TIM modules
Module
Module width
Module height
Max. depth
Communications module
TIM 3V-IE and
TIM 3V-IE Advanced
40 mm
125 mm
120 mm or 150 mm with
open front panel
Communications module
TIM 3, TIM 4 and TIM 4R-IE
80 mm
125 mm
120 mm or 180 mm with
open front panel
5.5.4
Connecting the TIM to the power supply
WARNING
Connecting the TIM module to a live power supply can damage the module. Connect the
module to the power supply only when the power supply is off.