Introduction to the SINAUT ST7 system
2.10 SINAUT ST7cc, the add-on for WinCC
SINAUT ST7 Station control system - System Manual
96
System Manual, 05/2007, C79000-G8976-C178-06
Note
The SINAUT ST7cc for WinCC expansion packet is described in detail in a separate manual.
To complete the introduction to the SINAUT ST7 system in this chapter, we will nevertheless
briefly outline the properties of the SINAUT ST7cc package.
2.10.2
The special properties of SINAUT ST7cc
Telecontrol master with user-friendly diagnostics
● Direct connection of SINAUT ST7 TIMs to ST7cc over MPI and Ethernet. A separate CPU
as telecontrol master is not required.
● Availability of the most important status information of each SINAUT ST7 or ST1
subscriber with visualization in WinCC using provided station typicals (picture typicals and
faceplates)
● Option of controlling SINAUT subscribers with these faceplates
● Identification of process values from subscriber stations with a disrupted connection to
ST7cc
● General request to affected stations following data transfer problems to allow the process
image to be updated in ST7cc
● For diagnostic purposes: Selective recording of message traffic for individual or all
SINAUT subscribers. Message visualization and evaluation is the same as with the TIM
message monitor.
● Time synchronization by ST7cc for the TIMs connected to the ST7cc PC over Ethernet
Preprocessing of process data
Preprocessing can be configured for binary, analog, and counted values. This takes into
account the event time and adds the time stamp of the event time to related messages and
archive entries.
● Binary values
– Entry of current binary values in the assigned WinCC tags
– Entry of related messages into the WinCC message system taking into account the time
stamp supplied by SINAUT ST7 or ST1
● Analog values (instantaneous and mean values)
– Floating-point numbers, integer values
– Linear raw value scaling (raw value --> physical value)
– Entry of analog values (with or without linear raw value scaling) in the assigned WinCC
tags
– Entry of analog values (with or without linear raw value scaling) into the WinCC archive
taking into account the time stamp supplied by SINAUT ST7 or ST1.