Installation guide
3.6 Standalone TIM 4R-IE with an S7-400 or PC
SINAUT ST7 Station control system - System Manual
System Manual, 05/2007, C79000-G8976-C178-06
133
3.6
Standalone TIM 4R-IE with an S7-400 or PC
Introduction
In standalone mode, in other words, without an S7-300-CPU, the TIM 4R-IE is ideally suited
as a SINAUT communications processor for an S7-400 or for the PC of the ST7cc or ST7sc
control center. They are then linked over one of the Ethernet ports of the TIM.
With an S7-400, an Ethernet CP should be used as the interface. Direct connection of the
TIM 4R-IE to the PROFINET interface of an S7-400-CPU is not possible! The following
S7-400-CPUs can be linked over an Ethernet CP:
CPU 412-1
as of 6ES7 412-1XF00-0AB0
(Version 02)
CPU 412-2
as of 6ES7 412-2XG00-0AB0
(Version 01)
(CPU 413-1)
as of 6ES7 413-1XG00-0AB0
(Version 02)
(CPU 413-2)
as of 6ES7 413-2XG00-0AB0
(Version 03)
(CPU 414-1)
as of 6ES7 414-1XG00-0AB0
(Version 02)
CPU 414-2
as of 6ES7 414-2XG00-0AB0
as of 6ES7 414-2XJ00-0AB0
(version 03)
(version 01)
CPU 414-3
1)
as of 6ES7 414-3XJ00-0AB0
(Version 01)
(CPU 416-1)
as of 6ES7 416-1XJ00-0AB0
(Version 02)
CPU 416-2
as of 6ES7 416-2XK00-0AB0
(as of 6ES7 416-2XL00-0AB0)
(version 01)
(version 01)
CPU 416-3
as of 6ES7 416-3XL00-0AB0
(Version 01)
CPU 416F-2
as of 6ES7 416-2FK02-0AB0
(Version 01)
CPU 417-4
1)
as of 6ES7 417-4XL00-0AB0
1)
Fault-tolerant SINAUT solutions with a CPU 414-4H or CPU 417-4H are not possible!
With the SINAUT ST7cc or ST7sc control center system, the TIM 4R-IE is connected to the
Ethernet card of the control center computer over its Ethernet port.
Installation
When installed separately, the TIM is normally installed on a separate S7-300 standard rail,
when necessary along with a power supply module to supply the TIM with 24 V. If the
SINAUT MD2, MD3 or MD4 modems are used, they can also be installed on the same rail.
The bus module connector supplied with every TIM is not required here since the TIM and
modem are always interconnected over the 6NH7701-xxx connecting cable.
TIM 4R-IE with SIMATIC S7-400
The TIM 4R-IE is connected to a SIMATIC S7-400 over one of the Ethernet ports of the TIM.
With the S7-400, an Ethernet CP is used as the interface. Direct connection of the TIM 4R-IE
to the PROFINET interface of an S7-400-CPU is not possible!