Performance data
2.6 Characteristic data for PROFINET CBA
CP 443-1 Advanced (GX30)
30
Manual, 03/2019, C79000-G8976-C256-05
If one of the limit values specified for the interconnections is exceeded, they cannot be
downloaded to the module. When the interconnections are downloaded, the SIMATIC iMap
configuration tool generates an error message to this effect. If a limit value relating to the
number or size of components is exceeded, the CPU will not change to RUN!
Characteristic
Typical value
Limit value
with FB88
with FB90
PROFINET CBA
Number of remote interconnection
partners
32
64
Total of all attachments
600
600
Data length of all incoming attach-
ments
3200 bytes
8192 bytes
1452 bytes
Data length of all outgoing attach-
ments
3200 bytes
8192 bytes
1452 bytes
Data length for arrays and structures
(acyclic interconnections), maximum
2048 bytes
8192 bytes
*)
1452 bytes
Data length for arrays and structures
(cyclic interconnections), maximum
250 bytes
250 bytes
250 bytes
Data length for arrays and structures
(local interconnections), maximum
-
2400 bytes
1452 bytes
Remote interconnections with acyclic transmission
Scanning frequency: Scanning inter-
val, min.
Selectable values: 100, 200, 500 and
1000 ms
fast value: 20%
medium value: 40%
slow value: 40%
100 ms minimum
Number of incoming interconnections
64
150 maximum
Number of outgoing interconnections
64
150 maximum
Data length of all incoming intercon-
nections
2048 bytes
8192 bytes
1452 bytes
Data length of all outgoing intercon-
nections
2048 bytes
8192 bytes
Remote interconnections with cyclic transmission
Transmission frequency: Transmission
interval, min.
Selectable values: 8, 16, 32, 64, 128,
256 and 512 ms
fast value: 20%
medium value: 40%
slow value: 40%
8 ms minimum
Number of incoming interconnections
125
250
Number of outgoing interconnections
125
250
Содержание SIMATIC NET CP 443-1 Advanced
Страница 8: ...Preface CP 443 1 Advanced GX30 8 Manual 03 2019 C79000 G8976 C256 05 ...
Страница 48: ...Requirements for use 3 5 Programming CP 443 1 Advanced GX30 48 Manual 03 2019 C79000 G8976 C256 05 ...
Страница 116: ...Approvals CP 443 1 Advanced GX30 116 Manual 03 2019 C79000 G8976 C256 05 ...
Страница 126: ...Index CP 443 1 Advanced GX30 126 Manual 03 2019 C79000 G8976 C256 05 ...