Configuration and operation
6.13 Ping: Permitted length of ICMP packets
CP 443-1 Advanced (GX30)
86
Manual, 03/2019, C79000-G8976-C256-05
MIB files for your SNMP tools
If you use an SNMP tool, you will find the MIB files relevant to the CP in the STEP 7
installation in the following folder:
<Drive>\<Installation folder>\Siemens\Step7\S7DATA\snmp\mib
For the Automation System MIB, for example, these are the following files:
●
automationPS.mib
●
automationSmi.mib
●
automationSystem.mib
●
automationTC.mib
Further information
You will find further information in the manual /6/ (Page 118).
6.13
Ping: Permitted length of ICMP packets
Pings with a packet size of more than 1000 bytes are evaluated as an attack and filtered by
the CP. This response is intentional and improves the robustness of the CP in an industrial
environment.
A ping simply serves to check reachability. There is therefore no need to support extremely
long ICMP packets.
6.14
Use in the H system
H connections not via VPN
The CP does not support operation of H connections (fault-tolerant system S7-400H) within
a VPN tunnel.
S7 connections as H connections via ISO-on-TCP - adapting the monitoring time
When using the CP in the H system V4.5, you also have the option of creating fault-tolerant
S7 connections via ISO-on-TCP. When operating large numbers of connections via the CP,
it may be necessary to increase the monitoring time. Otherwise it is possible that some
connections cannot be established.
Содержание SIMATIC NET CP 443-1 Advanced
Страница 8: ...Preface CP 443 1 Advanced GX30 8 Manual 03 2019 C79000 G8976 C256 05 ...
Страница 48: ...Requirements for use 3 5 Programming CP 443 1 Advanced GX30 48 Manual 03 2019 C79000 G8976 C256 05 ...
Страница 116: ...Approvals CP 443 1 Advanced GX30 116 Manual 03 2019 C79000 G8976 C256 05 ...
Страница 126: ...Index CP 443 1 Advanced GX30 126 Manual 03 2019 C79000 G8976 C256 05 ...