Depending on the firmware version of the CPU you are using, set the monitoring time with
the following method:
●
H CPU with firmware as of V6.0
The setting is made in the properties parameters of the configured connection.
●
H CPU with firmware < V6.0
The setting is made in the properties parameters of the CP.
6.15
Using the CP for PROFINET CBA
To be able to use the CP 4431 Advanced with PROFINET CBA, you create your user
program with STEP 7 and configure the S7400 station.
You then configure the interconnections between the PROFINET CBA components with
SIMATIC iMap.
Note
Requirements
•
Configuration for PROFINET CBA is only possible with STEP 7 V5.5.
For details, see section Project engineering (Page 45)
•
Operation under PROFINET CBA is supported only via the PROFINET interface. The
following information on configuration therefore relates only to the configuration of the
PROFINET interface.
Note
PROFINET CBA versus security function
If you use PROFINET CBA, you cannot enable the CP for the "Security" functionality.
6.15.1
CBA interface in the user program
PN_InOut_Fast (FB90) / PN_InOut (FB88) and interface DB
The interface to the user program is the interface DB for PROFINET CBA. The PN_IO_X
(FB90) and PN_InOut (FB88) program blocks are responsible for transferring data from the
interface DB to the CP and from the CP to the interface DB.
Содержание SIMATIC NET CP 443-1 Advanced
Страница 8: ...Preface CP 443 1 Advanced GX30 8 Manual 03 2019 C79000 G8976 C256 05 ...
Страница 48: ...Requirements for use 3 5 Programming CP 443 1 Advanced GX30 48 Manual 03 2019 C79000 G8976 C256 05 ...
Страница 116: ...Approvals CP 443 1 Advanced GX30 116 Manual 03 2019 C79000 G8976 C256 05 ...
Страница 126: ...Index CP 443 1 Advanced GX30 126 Manual 03 2019 C79000 G8976 C256 05 ...