background image

Operation of Screen Objects

5-6

TP 170A Equipment Manual

Release 12/99

Message view

The TP 170A can display up to 16 messages in the message view. If more than 16
messages are present simultaneously on the operating unit, the oldest message in
the queue is deleted.

It is possible to define specific views of the messages to be displayed in the
message view. Various filter criteria is available for this in the configuration
software.

The following can be configured 

Message categories (event and system messages only)

Number of columns

Number of lines per message

Sorting (oldest or latest message at the top)

Maximum number of visible messages

The figure illustrates an example of a message view with the configured columns

Date

Time

Message number

Message status

Message text

12.12.99 14:27:06 110001 K 
Change to operating status ’online’

12.12.99 14:27:07 140001 K 
Connection discontinued: Station 2, Rack 0, Slot 0

Synchronize date and time

In order to synchronize the date and time on the operating unit with the PLC, the
area pointer 

Date/Time PLC must be set up in the project in ProTool/Pro CS.

During runtime, the operating unit accesses these data areas in the PLC for
reading purposes and synchronizes the date and time in the configured acquisition
cycle with the PLC. This data is provided, for example, in the message time
stamps issued in the message display.

Detailed information concerning the area pointers is provided in the
ProTool Configuring Windows-based Systems user’s guide, in the configuration
software online help and in the 

Communication for Windows-based Systems user’s

manual.

CuuDuongThanCong.com

https://fb.com/tailieudientucntt

Содержание SIMATIC HMI TP 170A

Страница 1: ...eration of Screen Objects 5 System Settings 6 Installation 7 Unit Description 8 Maintenance Upkeep 9 Operating System Update 10 Appendices A E Glossary Index Release 12 99 6AV6591 1DC11 0AB0 Touch Panel TP 170A Equipment Manual SIMATIC HMI CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 2: ...s The registered trademarks of Siemens AG are listed in the Preface Some of the other designations used in these documents are also registered trademarks the owner s rights may be violated if they are used be third parties for their own purposes Impressum Editor and Publisher A D PT1 D1 Safety Guidelines This manual contains notices which you should observe to ensure your own personal safety as we...

Страница 3: ... provided in Appendix E Organization of the manual The TP 170A equipment manual is organized into the following chapters Chapter Contents 1 2 Overview of features and functional scope of the TP 170A 3 6 Commissioning operation and system settings 7 9 Mechanical and electrical installation unit description as well as maintenance and upkeep of the TP 170A 10 Information on the operating system updat...

Страница 4: ...History The various releases of this manual correspond to the following versions of the ProTool configuration software Release Comment ProTool version 12 99 First release of the TP 170A equipment manual From Vers 5 2 Trademarks The following names are registered trademarks of the Siemens AG S SIMATICR S SIMATIC HMIR S HMIR S ProToolR S ProTool LiteR S ProTool ProR S SIMATIC Multi PanelR S SIMATIC ...

Страница 5: ...to 17 00 Local time Mo Fr 8 00 to 19 00 Local time Mo Fr 8 30 to 17 30 Telephone 49 911 895 7000 Telephone 1 423 461 2522 Telephone 65740 7000 Fax 49 911 895 7002 Fax 1 423 461 2231 Fax 65740 7001 E Mail simatic support nbgm siemens de E Mail simatic hotline sea siemens com E Mail simatic hotline sae siemens com SIMATIC Premium Hotline charged only with SIMATIC Card Time Mo Fr 0 00 to 24 00 Teleph...

Страница 6: ...products through its Online services as follows Up to date general information is provided in Internet under http www ad siemens de simatic via the Fax Polling under 08765 93 02 77 95 00 Up to date product information and downloads for practical use can be found in Internet under http www ad siemens de support html 00 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 7: ...agnetic Compatibility EPROM Electric Programmable Read Only Memory ESD Electrostatic Sensitive Device HMI Human Machine Interface IF Interface LCD Liquid Crystal Display LED Light Emitting Diode MPI Multipoint Interface SIMATIC S7 OP Operator Panel PC Personal Computer PLC Programmable Logic Control PPI Point to Point Interface SIMATIC S7 PU Programming Unit RISC Reduced Instruction Set Computing ...

Страница 8: ...Preface vi TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 9: ...eration of Screen Objects 5 1 5 1 Overview of Screen Objects 5 2 5 2 Status Button 5 3 5 3 Messages 5 5 5 4 Logging On and Off from the Operating Unit 5 7 6 System Settings 6 1 6 1 Setting an Operating Mode 6 2 6 2 Screen Settings 6 3 7 Installation 7 1 7 1 Mechanical Installation 7 2 7 2 Electrical Installation 7 4 7 2 1 Connect Configuration Computer 7 7 7 2 2 Connect PLC 7 8 8 Unit Description ...

Страница 10: ...12 99 9 Maintenance Upkeep 9 1 10 Operating System Update 10 1 Appendices A Technical Data A 1 B Interface Assignment B 1 C System Messages C 1 D ESD Guidelines D 1 E SIMATIC HMI Documentation E 1 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 11: ...g It provides a realistic graphical representation of the machine or system to be monitored Its area of use includes implementation in machine and apparatus construction as well as in the packing and electronics industry The high degree of protection IP65 on the front side and non implementation of moving storage media such as hard disks and floppy disks ensure the TP 170A is also suitable for use...

Страница 12: ...ents by using the configuration software ProTool Lite ProTool and ProTool Pro CS from Version 5 2 The TP 170A can be used to control and monitor the process intuitively Setpoint values or control element settings for instance can be modified by entering values or touching configured buttons display processes machines and systems graphically visualize operating and alarm messages and process tags e...

Страница 13: ...he operating unit refer to Configuration phase in Figure 1 1 Once the project has been successfully downloaded connect the operating unit to the PLC The operating unit can then communicate with the PLC and respond according to the information configured for running the program in the PLC refer to Process control phase in Figure 1 1 Create project data Store project data Test project Simulateprojec...

Страница 14: ...el Back lighting CCFL tube Half Brightness Life1 approx hr 50 000 1 Refer to the Glossary for a definition Further information Detailed information on the technical data of the operating unit is provided in Appendix A of this manual Information on the configuration of the operating unit is provided in the ProTool Configuring Windows based Systems user s guide Connection of the operating unit to th...

Страница 15: ...er 100 Display In message display Type of display First Last Message text length 70 characters Pending message events 16 Process values in message text 8 Message acquisition Time of occurrence Date and time Screens View 4 Screen objects Output field Input field Text Graphics Status button Bar Message view Limit value monitoring Inputs outputs 4 Password protection Passwords 1 Screen settings Contr...

Страница 16: ...Functionality 2 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 17: ...r This chapter provides information on starting up the operating unit for the first time Page 3 2 restarting the operating unit from Page 3 3 the options for Download mode from Page 3 5 testing a configuration Page 3 7 3 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 18: ...the configuration computer or the button Cancel is pressed If the message Connecting to host does not appear it is possible that the option for Download mode has been set incorrectly refer to the note on Page 3 6 3 If data is to be transferred via an MPI connection set the following parameters on the configuration computer OP Address 1 Transmission rate 187 5 kBaud Start the data transfer to the o...

Страница 19: ... the Download button to set the operating unit to Download mode before it is initialized The operating unit displays the message Connecting to host until it receives data from the configuration computer or the button Cancel is pressed If the message Connecting to host does not appear it is possible that the option for Download mode has been set incorrectly refer to the note on Page 3 6 4 If downlo...

Страница 20: ... are defined in the Configuration menu Figure 3 2 MPI connection Option MPI Transfer Enable activated Option MPI Transfer Remote activated Serial connection Option Serial Transfer Enable activated Option Serial Transfer Remote activated A detailed description of the possible settings in the Configuration menu is provided on Page 3 5 Note The bus parameters e g MPI address baud rate etc are read ou...

Страница 21: ...ed to a specific connection type so that downloading is only performed via a serial or an MPI connection Call in the Configuration menu The options for Download mode can only be set when the operating unit is in its initialization phase During the operating unit initialization phase the Start menu illustrated in Figure 3 1 appears briefly Touch the Config button to call in the Configuration menu d...

Страница 22: ...n when the Serial Transfer Enable option is active When this option is active the operating unit automatically switches from normal operation to Download mode in the case of serial transfer from the configuration computer Use the OK button to confirm the current settings for downloading options The Configuration menu is closed and the Start menu illustrated in Figure 3 1 is displayed Note If both ...

Страница 23: ...PLC is simulated by the software Start the simulator by clicking on the symbol depicted on the left or by using the menu command File Test Start simulator Detailed information on operating the simulator is provided in the ProTool Configuring Windows based Systems user s guide and in the configuration software online help Note For the test phase of a configuration it is recommended to initiate Down...

Страница 24: ...Commissioning 3 8 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 25: ...apter This chapter contains information on how to operate touch elements from Page 4 2 enter values from Page 4 4 operate screens Page 4 6 Information regarding operation for special screen objects is provided in Chapter 5 4 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 26: ... sensitive operating elements provided on the touch panel screen such as buttons and input fields Their operation is basically no different from pressing conventional keys Touch elements are operated by touching them lightly with your finger or a suitable object Note Never use pointed or sharp instruments to operate the Touch Panel to prevent damage to the plastic surface of the touch screen Cauti...

Страница 27: ...ntation is distinguished according to the statuses touched and untouched Examples of representation are illustrated below by means of the Status button Untouched Touched Input fields After an input field has been touched the system keyboard illustrated in Figure 4 1 appears as the operation acknowledgement Password protected operating elements If an operating element is touched which has been assi...

Страница 28: ... disappears and the entered value is accepted in the input field System keyboard The buttons available for operation on the system keyboard are dependent on the type of value to be entered Buttons which are available for operation are highlighted and those not available appear simply as empty areas Figure 4 1 illustrates an example of the system keyboard for entering decimal values Table 4 1 expla...

Страница 29: ...m keyboard Delete character Delete the character to the left of the input position Enter Confirm input and close the system keyboard Enter value Characters entered are aligned to the right On entering a new character all those already entered are shifted one position to the left pocket calculator format On exceeding the maximum number of characters the last character entered is overwritten Limit v...

Страница 30: ... of dynamically positioning screen partitions but to the connection to the PLC Static partitions e g text and graphics are not updated by the PLC Dynamic partitions e g input and output fields and bars can be linked to the PLC and display current values constantly read in from the PLC memory Their connection to the PLC is established by means of tags Screen objects Various screen elements are used...

Страница 31: ...reen objects which may be contained in a configuration and explains their operation It provides the following information a summary of screen objects Page 5 2 the Status button from Page 5 3 messages from Page 5 5 logging in and out of the operating unit Page 5 7 5 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 32: ... lines and cannot be altered on the operating unit Graphics Graphics can be used in the configuration e g to represent a system or as an illustrative symbol for configured display and operating elements Status button A Status button is a display and input element with two different statuses Notes on the Status buttons is provided on Page 5 3 Bar Bars represent values from the PLC as rectangular ar...

Страница 33: ...hics for the two statuses ON and OFF Option push button The Status button reacts as a key in button When pressed the Status button changes to the status ON It remains in this status as long as the Status button is pressed When released it automatically switches back to OFF Event related initiation Use the configuration software to assign the Status button one or more functions and to define which ...

Страница 34: ...n software can be used to assign different text or graphics to indicate the status of the button during runtime Figure 5 1 illustrates an example of a Status button when pressed left and not pressed right Figure 5 1 The two statuses relate to the Status button when the Switch option is set CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 35: ... faults for example A time period can be considered for system messages in the configuration software This defines how long a system message appears on the operating unit A list of the most important system messages is provided in the Appendix C Message events These messages are triggered according to events Message events on the TP 170A include Message arrival A message which has been triggered i...

Страница 36: ...ate Time Message number Message status Message text 12 12 99 14 27 06 110001 K Change to operating status online 12 12 99 14 27 07 140001 K Connection discontinued Station 2 Rack 0 Slot 0 Synchronize date and time In order to synchronize the date and time on the operating unit with the PLC the area pointer Date Time PLC must be set up in the project in ProTool Pro CS During runtime the operating u...

Страница 37: ...configuration In order to access a password protected operating element during runtime it is necessary to log on on the operating unit It is then possible to access all password protected operating elements up to the point of logging off from the operating unit Logoff In order to rule out operation by unauthorized personnel the logon should not remain active on the operating unit for too long a pe...

Страница 38: ...Operation of Screen Objects 5 8 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 39: ...gs In this chapter This chapter provides information on the following general settings which can be modified on the operating unit online Operating mode Page 6 2 Screen contrast and calibration Page 6 3 6 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 40: ...erating unit and PLC The operating unit can be operated but processes cannot be operated or visualized Online mode When using this mode processes can be operated and visualized without restriction There is a logical connection between the operating unit and PLC or the operating unit attempts to establish one Online mode is the predefined operating mode each time the operating unit is started up Do...

Страница 41: ...tings in the initialization phase Step Action 1 Switch on the power supply for the operating unit 2 During the initialization phase the menu illustrated in Figure 6 1 appears briefly Touch the Config button to call in the Configuration menu displayed in Figure 6 2 3 Touch the Contrast and Contrast buttons to change the contrast setting of the screen Note Touch the buttons sufficiently long enough ...

Страница 42: ...d while the system is actually running A condition for this is that the following functions are linked to operating elements in the actual project Adjust_Contrast Touch_Calibration Save settings The operating unit saves the current screen settings backed up against a power failure and sets them automatically when the system is switched on again CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 43: ...his chapter This chapter provides information on the installation of the operating unit from Page 7 2 electrical connections to the power supply Page 7 6 the configuration computer Page 7 7 the PLC Page 7 8 7 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 44: ...n the front plate of the operating unit is fitted correctly Caution S The unit must be brought to room temperature before it is commissioned If condensation forms do not switch the unit on until it absolutely dry S To prevent the operating unit overheating during operation the angle of inclination from vertical installation may not exceed a maximum of 35_ do not expose the operating unit to direct...

Страница 45: ...hooks of the screw type clamps enclosed in the corresponding recesses in the housing of the operating unit The individual positions are indicated in the figure by means of arrows Front panel Operating unit 3 Use a screwdriver to tighten the operating unit from the rear in the front panel Note Make sure the seal is seated correctly against the front panel Never apply torques greater than 0 5 Nm in ...

Страница 46: ...rror free operation is an EMC compatible hardware design of the PLC and the use of interference proof cables The guidelines on interference free design of the PLCs apply equally to installation of the operating unit Caution Only shielded cables are permitted for all signal connections Screw or lock all plug connections Do not install signal lines in the same cable ducts as power cables Siemens AG ...

Страница 47: ...ly Optionally PLC PROFIBUS DP SIMATIC S7 PC PU 7xx DIL switches Settings see Page 7 9 Groundingconnection PC PU 7xx Configuration computer RS485 RS232 Figure 7 1 Configuration options Detailed information on connection options is provided in the following pages Information on the connection plug pin assignment for the interfaces are provided in Appendix B of this manual CuuDuongThanCong com https ...

Страница 48: ...r to the technical data in Appendix A for information on the power supply requirements Caution When using a 24 V supply make sure that the extra low voltage is isolated safely Use only power supply units complying with IEC 364 4 41 or HD 384 04 41 VDE 0100 Part 410 The supply voltage must be within the specified voltage range Voltages outside this range can cause malfunctions Grounding connection ...

Страница 49: ...ownload the project data Standard cables are available for the connections shown refer to the ST80 catalog COM IF1A PC PU 7xx Operating unit RS232 1 IF1B Optionally PROFIBUS DP MPI COM PC PU 7xx DP 1 Operating system update only via RS232 refer to Chapter 10 2 Any PROFIBUS DP bus terminal RS485 2 Figure 7 2 Connection configuration diagram for configuration computer CuuDuongThanCong com https fb c...

Страница 50: ...bles are available for the connections shown refer to the ST80 catalog 1 Only use approved cables for connection to the SIMATIC S7 2 Any PROFIBUS DP bus terminal 3 The 1F1B interface can be configured by means of the DIL switch Page 7 9 2 Operating unit IF1B3 Optionally PROFIBUS DP MPI DP RS485 SIMATIC S71 Figure 7 3 Connection configuration for PLCs CuuDuongThanCong com https fb com tailieudientu...

Страница 51: ...efault the RTS signal is not required by the communication peer The table shows the permissible DIL switch settings Communication Switch Setting PLC RS422 Operatingunit ON 1 2 3 4 DP MPI Operatingunit ON 1 2 3 4 RTS on Pin 4 default RTS on Pin 9 same as PU ON 1 2 3 4 PLC No RTS on connector1 ON 1 2 3 4 PLC MPI Standardcable Operatingunit ON 1 2 3 4 No RTS on connector1 1 State on delivery CuuDuong...

Страница 52: ...Installation 7 10 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 53: ...Manual Release12 99 Unit Description In this chapter This chapter provides information on Dimensions Page 8 2 Connection elements Page 8 3 Communication options Page 8 4 8 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 54: ...ons 196 45 212 6 156 140 Figure 8 1 TP 170A dimensions Mounting cut out For installation in the front panel the operating unit requires a mounting cut out WxH of 198 1 mm x 142 1 mm The thickness of the front panel must not exceed 6 mm CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 55: ... Level Usage IF1A RS232 PC PU IF1B RS485 floating PLC PC PU Grounding connection For connection to cabinet ground Power supply2 Connection for power supply 24 V DC DIL switch3 To configure interface IF1B 1 Connection pin assignment see Appendix B 2 Connection pin assignment see 7 6 3 Switch settings see Page 7 9 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 56: ...ment Manual Release12 99 8 3 CommunicationOptions Device Connection Interface SIMATIC S7 MPI PROFIBUS DP IF1B IF1B Configuration computer PC PU RS232 IF1A MPI DP IF1B PROFIBUS DP IF1B CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 57: ...y coming into contact with the touch screen Only use water and washing up liquid or screen cleaning foam to dampen cloths Never spray the cleaning agent directly onto the screen but onto the cleaning cloth Never use aggressive solvents or scouring powder Protective foil A protective foil is available for the operating unit refer to the ST80 catalog The foil prevents the screen being scratched and ...

Страница 58: ...Maintenance Upkeep 9 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 59: ...tion software installation CD It is located in the directory Images TP170A Vx_x 4 Select the menu item File Open and open the image file which corresponds to the operating unit file extension img The image files are located in the same directory as the utility program PTUpdate The applicable image file can be recognized by its file name which contains the name of the operating unit When the image ...

Страница 60: ...Operating System Update 10 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 61: ...APPENDICES A Technical Data B Interface Assignments C System Messages D ESD Guidelines E SIMATIC HMI Documentation CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 62: ...APPENDICES J 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 63: ...his Appendix This section of the Appendix contains technical data on the TP 170A concerning Housing Processor Memory Software Display Power supply Ambient conditions Noise immunity Noise transmission Approvals A CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 64: ...MB Software Operating system MS WindowsR CE Display LCD type STN LCD Blue mode Active screen area B H in mm 116 x 87 mm 5 7 Resolution horizontal x vertical 320 x 240 pixels Monochrome 4 level Back lighting CCFL tube Half Brightness Life1 Approx 50 000 h 1 Definition refer to Glossary Power supply Rated voltage 24 V DC Permissible voltage range 18 0 30 0 V DC Max permissible transients 35 V 500 ms...

Страница 65: ...age 20 60 C Relative humidity Operation Shipping storage 20 85 no condensation 5 90 no condensation Shock loading Operation Shipping storage 15 g 11 msec 25 g 6 msec Vibration Operation 0 035 mm 10 58 Hz 1 g 58 500 Hz Shipping storage 3 5 mm 5 8 5 Hz 1 g 8 5 500 Hz Barometric pressure Operation Shipping storage 706 to1030 hPa 581 to 1030 hPa Compliance of the named products with the regulations of...

Страница 66: ...00 4 3 10 V m 80 AM 1 kHz Pulse modulation ENV 50204 900 MHz 5 MHz 10 V meff 50 ED 200 Hz RF conduction EN 61000 4 6 150 kHz 80 MHz 10 V 80 AM 1 kHz Burst interference Supply lines Process data lines Signal lines EN 61000 4 4 2 kV 2 kV 1 kV Radio interference Radio interference level complying to EN 55011 Class A CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 67: ...1 Hazardous classified Locations Class I Division 2 Group A B C D Warning Personal injury and equipment damage can occur Personal injury and equipment damage can occur in hazardous areas if a plug connection is disconnected from the operating unit while the system is running In hazardous areas always switch off the power supply to the operating unit before disconnecting plugs Warning DO NOT DISCON...

Страница 68: ...Technical Data A 6 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 69: ...ND 6 7 RTS 8 CTS 9 IF1B Table B 2 Pin assignment of the 9 pin Sub D socket Pin PROFIBUS DP MPI RS422 RS485 1 2 GND 24 V 3 Data B TxD LTG B 4 RXD 1 RTS AS 1 5 GND floating 6 5 V floating 7 8 Data A TXD LTG A 9 RXD 1 RTS PU 1 1 Can be configured by DIL switches refer to Page 7 9 B 5 1 9 6 5 1 9 6 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 70: ...Interface Assignment B 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 71: ...oncerning the category to which a system message belongs is included in the message number VVVVVV Message text Messagenumber 01 Printer 02 Scripts 03 Scale 06 Win32functions 07 Win32functions 08 Archives 11 Function 12 Trends 13 Systeminformation 14 Channels and connections S7 15 Channels and connections AS511 16 Networking 17 S7 diagnostics 18 Miscellaneous 19 Tags and area pointers 20 PLCcoordin...

Страница 72: ...nes in text mode e g messages is full Up to 1000 lines can be buffered Do not issue print jobs so quickly in succession 10005 Lines of text can be buffered again 10006 The Windows print system reports an error For information on the cause refer to the text printed and if available the error number Printing is not performed or it is incorrect Repeat the action if necessary 20010 A fault has occurre...

Страница 73: ... could not be executed since the parameters could not be converted to a common tag type Check the parameter types in the configuration 50000 The operating unit receives data faster than it is capable of processing Therefore no further data is received until the data currently available has been processed Data exchange then resumes 50001 Data exchange has been resumed 60000 This message is generate...

Страница 74: ...be set Under Windows NT The user executing ProTool Pro RT must be assigned the rights to modify the system time from Windows NT administration user manager guidelines 70015 The system time could not be read because Windows rejects the reading function 70016 An attempt was made to select a screen by means of a function or job This is not possible because the screen number specified does not exist O...

Страница 75: ...the archives are separated from the DB layer and all connections terminated e g after executing the function Close_Archives Values are temporarily buffered and written in the tables when the connection is re established There is no connection to the storage medium and a change can take place 80020 The max number of simultaneously activated copy actions has been exceeded Copying is not executed Wai...

Страница 76: ...g mode is now offline 110004 The operating status of the PLC specified is changed by the function PLC_Connect_Isolate The operating mode is now online 110005 An attempt was made to use the function PLC_Connect_Isolate to switch the specified PLC to operating mode online although the entire system is in operating mode offline This switch over is not permissible The PLC remains in operating mode off...

Страница 77: ...interface Restart the system 140005 No tag updating or writing is executed because the address of the operating unit is incorrect possibly too high Use a different operating unit address Check the connection and whether the PLC is switched on Check the parameter definitions in the Control Panel using Set PU PC interface Restart the system 140006 No tag updating or writing is executed because the b...

Страница 78: ...aster is connected to the network deactivate the option Is not active as the only master in Set PU PC interface If the network has more than one master switch this master on Do not modify any settings here otherwise a bus fault may occur 140011 No tag updating or writing is executed because communication is interrupted Check the connection and that the communication peer is switched on 140012 Ther...

Страница 79: ...e is no connection to the server because the server identification CLS ID cannot be established Values cannot be read or written Check the access rights 160011 There is no connection to the server because the server identification CLS ID cannot be established Values cannot be read or written Check for example whether S the server name is correct S the computer name is correct S the server is regis...

Страница 80: ...is updated following an error status after the cause of the last error state has been eliminated return to normal operation 190002 The tag is not updated because communication to the PLC has been switched off Switch on communication via the function Set Online 190004 The tag is not updated because the configured address is not available for this tag Check the configuration 190005 The tag is not up...

Страница 81: ...ng Check the value range or type of the variable 190100 The area pointer is not updated because the configured address for this area pointer is not available Type 1 Event messages 2 Alarm messages 3 PLC acknowledgment 4 Operating unit acknowledgment 5 LED assignment 6 Trend request 7 Trend transfer 1 8 Trend transfer 2 No is the consecutive number displayed in ProTool Pro Check the configuration 1...

Страница 82: ... PLC in an area which can be written to read from 210002 Jobs are not executed because the address format of the area pointer does not match the internal storage format Internal error 210003 The job mailbox is processed again because the last error status has been eliminated return to normal operation 210004 It is possible that the job mailbox is not processed 210005 A PLC job was triggered by an ...

Страница 83: ...ejected and the previous value is specified again Either the value range has been exceeded or impermissible characters were entered Enter a permissible value 230002 Since the current password level is inadequate or the password dialog box was closed with ESC the entry is rejected and the previous value is specified again Activate an adequate password level using Login 230003 Changeover to the spec...

Страница 84: ...el 270000 A tag is not displayed in the message because it attempts to access an invalid address in the PLC Check whether the data area for the tag exists in the PLC the configured address is correct or the value range for the tag is correct 270001 There is a unit dependent limit as to how many messages may be queued simultaneously in order to be displayed see GHB This limit has been exceeded The ...

Страница 85: ...he message can be entered in the message buffer for up to four more failed tags if necessary After that the message number 290003 is issued Check in the configuration that the address has been set up in the PLC 290001 An attempt has been made to assign a value to a tag which is outside the value range permitted for this type The message can be entered in the message buffer for up to four more fail...

Страница 86: ...gned The value is rejected Remove the specified data record tag in the specified recipe from the project 290010 The storage location configured for the recipe is not permitted Possible cause Impermissible characters write protected data medium full or does not exist Check the path specification configured 290011 The data record specified by the number does not exist Check the source for the number...

Страница 87: ...record although the data mailbox is not free at present This error may occur in the case of recipes for which downloading with synchronization has been configured Set the data mailbox status to zero 290027 No connection to the PLC can be established at present Therefore the data record can neither be read nor written Possible cause No physical connection to the PLC no cable plugged in cable is def...

Страница 88: ...ad written without errors The action was canceled Check the specified line column 300000 Process monitoring e g with PDiag or S7 Graph has been programmed incorrectly More messages are displayed simultaneously than specified in the technical data related to the CPU The CPU cannot manage subsequent Alarm_S messages and transfer them to the operating units Modify the configuration in the CPU 310000 ...

Страница 89: ...sages related to internal errors 1 Start up the operating unit again 2 Download the configuration again 3 Switch the operating unit off stop the PLC and then restart both 4 If the error occurs again please contact the SIMATIC Customer Support Make reference to the specified error number and message tags CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 90: ...System Messages C 20 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...

Страница 91: ...vices and thus to the contact sensitivity of the assemblies concerned ESDs may be destroyed by voltages and energies well below the perception threshold of persons Voltages of this kind occur as soon as a device or an assembly is touched by a person who is not electrostatically discharged Devices exposed to such overvoltages cannot immediately be detected as defective in the majority of cases sinc...

Страница 92: ... conductive ESD cellular material ESD bags ESD shipping containers Do not place assemblies near visual display units monitors or television sets minimum distance to screen 10 cm Measuring and modifying ESD assemblies Perform measurements on ESD assemblies only when the measuring instrument is grounded for example by means of a protective conductor or the measuring head has been briefly discharged ...

Страница 93: ...omponents User s Guides for Configuration software Runtime software Communication between PLCs and operating units Equipment Manuals for the following operating units SIMATIC PC MP Multi Panel OP Operator Panel TP Touch Panel TD Text Display PP Push Button Panel Online Help on the configuration software Start up Guides First Steps Overview of complete documentation The following table provides an ...

Страница 94: ... information on installation basic principles of configuration a detailed description of configurable objects and functions This documentation is valid for graphic display operating units ProTool Configuring Text based Displays User s Guide Configurers Provides information on working with the ProTool Lite configuration software It contains information on installation basic principles of configurat...

Страница 95: ... operating instructions instructions for connecting the PLC printer and programming computer maintenance instructions OP 37 Pro Equipment Manual Commissioning engineers Users Describes the hardware installation and inclusion of upgrades and options for the OP 37 Pro TP 27 TP 37 Equipment Manual OP 27 OP 37 Equipment Manual OP 25 OP 35 OP 45 Equipment Manual OP 7 OP 17 Equipment Manual OP 5 OP 15 E...

Страница 96: ... Allen Bradley PLC 5 SLC 500 Mitsubishi FX Telemecanique TSX This documentation describes the configuration and parameters required for connecting the devices to the PLC and the network user data areas used for exchanging data between operating unit and PLC Other PLCs Online Help Programmers Provides information on connecting devices to PLCs such as OPC Mitsubishi Allen Bradley Telemecanique Modic...

Страница 97: ...ntain current measured values Since alarm messages indicate abnormal operating statues they must be acknowledged Alarm time Time interval between the arrival and departure of an alarm message Area pointer Defines a memory area in the PLC for data exchange between the PLC and operating unit Bar graphs Represent values from the PLC as rectangular areas This is a way of displaying filling levels or w...

Страница 98: ...ransfer of run capable project data to the operating unit Connect the operating unit to the configuration computer with a standard cable beforehand Download mode Operating unit operating mode in which data can be downloaded from the configuration computer to the operating unit also refer to Download Event message Provides information on the operating unit concerning the operating statuses of the m...

Страница 99: ... tube only achieves 50 of the original value Help text Configurable additional information on messages screens and fields The help text concerning an alarm message can for example contain information on the cause of the fault and methods of elimination Icon Configured graphic symbol identifying the function of a function key Input field Enables the user to enter values which are subsequently downl...

Страница 100: ...tor A graphical symbol displayed on the operating unit when at least one alarm message is present Message logging Printout of alarm and event messages parallel to their display on the operating unit display Multi Panel Multi functional configurable operating unit with graphics display and WindowsR CE operating system for operating and monitoring machines and systems Normal operation Operating unit...

Страница 101: ...est level to Level 9 highest level The password level linked to the password allocates the rights to execute functions on the operating unit belonging to that level or lower PCL Hewlett Packard Printer Control Language PCMCIA Personal Computer Memory Card International Association Joint operation of computer companies with the aim of defining one international standard for memory cards and PC expa...

Страница 102: ...ammable system PLC from the SIMATIC S7 series SIMATIC S7 200 300 400 ProTool Full graphics based configuration software for the whole SIMATIC HMI unit range and for Windows based systems Remaining buffer Configurable size of the message buffer In the case of buffer overflow the operating unit deletes message events until the configured remaining buffer capacity is reached RS232 Standard interface ...

Страница 103: ...ment which can have one of two states ON and OFF i e touched and untouched Text or graphics can be configured for both states which then appear on the Status buto Status Force tag Screen object with which individual address areas in the connected SIMATIC S5 or SIMATIC S7 can be accessed for reading and writing directly from the operating unit Superuser A user with permissions to trigger functions ...

Страница 104: ...on is made between global tags process tags and local tags Touch panel This is an operating unit without a keyboard The touch panel abbreviated to TP is operated via the contact sensitive screen elements Trend curve Represents values from the PLC on the screen as a continuous line or bar TTY Standard interface for serial data transfer at a defined current level Transmitter and receiver are electri...

Страница 105: ...tion options 8 4 Compatibility conflict 3 2 3 3 10 1 Condensation 7 2 Conduction RF A 4 Configuration Load 3 2 Simulation 3 7 Test 3 7 Configuration computer 1 3 7 5 Connect 7 7 Configuration menu 3 5 6 3 Configuration options 7 5 Configuration phase 1 3 Configuration software 1 2 Configure Interface IF1B 7 9 Conflict Compatibility 3 2 3 3 10 1 Connect Configuration computer 7 7 PLC 7 8 Connecting...

Страница 106: ...g 7 6 Grounding connection 7 5 7 6 8 3 Grounding screw 7 6 Guidelines EEC A 3 ESD D 1 H Half Brightness Life 1 4 Hazardous area A 5 Hexadecimal digits enter 4 5 Housing A 2 Humidity A 3 I IF1A interface Assignment B 1 IF1B interface Assignment B 1 Initial startup 3 2 Input cancel 4 5 confirm 4 5 Input field 4 4 5 2 Installation 7 1 Configuration computer 7 7 Electrical 7 4 In front panels 7 3 Mech...

Страница 107: ...6 2 Online 6 2 Setting 6 2 Operating Screens 4 6 Operating system A 2 Operating system update 10 1 Operation general 4 1 Screen objects 5 1 Unauthorized 5 7 Operation acknowledgement 4 3 Optimization Contrast 6 3 Output field 5 2 Overheating 7 2 P Password protection 2 1 5 7 PC 1 3 connection 7 7 Pin array 7 6 Pin assignment B 1 Plan view TP27 6 8 2 PLC 7 5 Connect 7 8 Plug connections 7 4 Pocket ...

Страница 108: ...atic discharge A 4 Static screen partitions 4 6 Status button 5 2 5 3 Structure of the documentation E 1 Sub D socket B 1 Sunlight 7 2 Switch Status button 5 3 Switch settings DIL switch 7 9 Synchronize Date Time 5 6 System keyboard 4 4 System messages 5 5 List C 1 System settings 6 1 T Target groups E 1 Technical Data A 1 Terminal block 7 6 Test Configuration 3 7 Text static 5 2 Thickness Front p...

Отзывы: