System Messages
C-5
TP 170A Equipment Manual
Release 12/99
Remedy
Effect/Cause
Number
80012
Archive values are stored in a buffer. If the
values are read to the buffer faster than they
can be physically written (e.g. using a hard
disk), overloading may occur and recording
is then stopped.
Archive less values.
Or increase the recording interval.
80013
The overload status no longer applies.
Archiving resumes the recording of all
values.
–
80014
The same action was triggered twice in quick
succession. Since the process is already in
operation, the action is only carried out once.
–
80016
The archives are separated by the function
Close archive and the incoming entries
exceed the defined buffer size.
All the jobs in the buffer are deleted.
Reconnect the archives.
80017
The incoming entries cause the defined
buffer size to be exceeded. This can be
caused, e.g. by several copying actions
being activated at the same time.
All the copy jobs in the buffer are deleted.
Terminate the copy process.
80018
All the archives are reconnected by means of
the DB layer, e.g. after executing the function
Open_Archives.
Values are then written back into the tables.
–
80019
All the archives are separated from the DB
layer and all connections terminated, e.g.
after executing the function
Close_Archives.
Values are temporarily buffered and written in
the tables when the connection is
re-established.
There is no connection to the storage
medium and a change can take place.
–
80020
The max. number of simultaneously
activated copy actions has been exceeded.
Copying is not executed.
Wait until the current copying actions have
been completed and restart the last copy
action.
80021
An attempt was made to delete an archive
which is still involved with a copy action.
Deletion has not been executed.
Wait until the current copying action has
been completed and restart the last action.
80022
An attempt was made to start a sequence
archive, which is not a sequence archive,
from an archive using the function
Start_Sequence_Archive.
No sequence archive is created.
Check the project for the following:
S
the function
Start_Sequence_Archive is
correctly configured.
S
the variable parameters are being
correctly provided at the operating unit.
80023
An attempt was made to copy an archive to
itself.
The archive is not copied.
Check the project for the following:
S
the function
Copy_Archive is correctly
configured.
S
the variable parameters are being
correctly provided at the operating unit.
Содержание SIMATIC HMI TP 170A
Страница 8: ...Preface vi TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 16: ...Functionality 2 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 24: ...Commissioning 3 8 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 52: ...Installation 7 10 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 62: ...APPENDICES J 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 68: ...Technical Data A 6 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 90: ...System Messages C 20 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...