System Messages
C-4
TP 170A Equipment Manual
Release 12/99
Remedy
Effect/Cause
Number
70011
The system time could not be modified. This
may be due to the following:
S
an impermissible time was transferred in
the PLC job,
S
the Windows NT user has no user rights
to modify the system time.
Check the time which is to be set.
Under Windows NT: The user executing
ProTool/Pro RT must be assigned the rights
to modify the system time from Windows NT
(administration/user manager, guidelines).
70012
An error occurred when executing the
function “Exit Runtime” with the option “Exit
also Windows”.
Windows and ProTool/Pro RT are not
terminated.
A possible cause is that other applications
cannot be terminated.
Terminate all applications currently running.
Then terminate Windows.
70013
The system time could not be modified
because an invalid value was entered.
Incorrect separators may have been used.
Check the time which is to be set.
70014
The system time could not be modified. This
may be due to the following:
S
an impermissible time was transferred,
S
the Windows NT user has no user rights
to modify the system time,
S
Windows rejects the setting request.
Check the time which is to be set.
Under Windows NT: The user executing
ProTool/Pro RT must be assigned the rights
to modify the system time from Windows NT
(administration/user manager, guidelines).
70015
The system time could not be read because
Windows rejects the reading function.
–
70016
An attempt was made to select a screen by
means of a function or job. This is not
possible because the screen number
specified does not exist.
Or: a screen could not be generated due to
insufficient system memory.
Check the screen number in the function or
job with the screen numbers configured.
Refer the number to a screen, if necessary.
80001
–
Store the file or table by executing a ‘move’
or ‘copy’ function.
80002
A line is missing in the specified archive.
–
80003
The copying process for archiving was not
successful.
In this case, it is advisable to check any
subsequent system messages, too.
–
80006
Since archiving is not possible, this causes a
permanent loss of the functionality.
In the case of databases, check whether the
corresponding data source exists and start
up the system again.
80009
A copying action has been completed
successfully.
–
80010
Since the path was incorrectly entered in
ProTool, this causes a permanent loss of the
functionality.
Configure the path for the respective archive
again and restart the system when the full
functionality is required.
Содержание SIMATIC HMI TP 170A
Страница 8: ...Preface vi TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 16: ...Functionality 2 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 24: ...Commissioning 3 8 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 52: ...Installation 7 10 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 62: ...APPENDICES J 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 68: ...Technical Data A 6 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 90: ...System Messages C 20 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...