System Messages
C-15
TP 170A Equipment Manual
Release 12/99
Remedy
Effect/Cause
Number
280003
A connection is used which requires a
function module in the PLC.
The function block does not reply.
Check that the cable is plugged in, the PLC
is operational, the correct interface is used.
Reboot the system if the system message is
displayed continuously.
The remedy is dependent on the error code:
1:
The function block must set the COM bit
in the response container.
2:
The function block may not set the
ERROR bit in the response container
3:
The function block must respond within
the specified time (timeout)
4:
Establish an online connection to the
PLC
280004
The online connection to the PLC has been
interrupted. There is no data exchange at
present.
Check the PLC parameters in ProTool Pro:
baud rate, block length, station address.
Check that the cable is plugged in, the PLC
is operational, the correct interface is used.
Reboot the system if the system message is
displayed continuously.
290000
The tag could not be read or written. It is
assigned the start value.
The message can be entered in the
message buffer for up to four more failed
tags, if necessary. After that, the message
number 290003 is issued.
Check in the configuration that the address
has been set up in the PLC.
290001
An attempt has been made to assign a value
to a tag which is outside the value range
permitted for this type.
The message can be entered in the
message buffer for up to four more failed
tags, if necessary. After that, the message
number 290004 is issued.
Observe the value range for the tag type.
290002
It is not possible to convert a value from a
source format to a target format.
The message can be entered in the
message buffer for up to four more failed
tags, if necessary. After that, the message
number 290005 is issued.
Check the value range or type of the
variable.
290003
This message is issued when message
number 290000 is triggered more than five
times.
In this case, no further individual messages
are generated.
Check in the configuration that the tag
addresses have been set up in the PLC.
290004
This message is issued when message
number 290001 is triggered more than five
times.
In this case, no further individual messages
are generated.
Observe the value range for the tag type.
Содержание SIMATIC HMI TP 170A
Страница 8: ...Preface vi TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 16: ...Functionality 2 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 24: ...Commissioning 3 8 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 52: ...Installation 7 10 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 62: ...APPENDICES J 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 68: ...Technical Data A 6 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 90: ...System Messages C 20 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...