System Messages
C-17
TP 170A Equipment Manual
Release 12/99
Remedy
Effect/Cause
Number
290022
Acknowledgement that downloading of data
records from operating unit to PLC has been
terminated due to an error.
Check the configuration:
S
have the tag addresses been set up in
the PLC?
S
does the recipe number exist?
S
does the data record number exist?
S
has the function parameters “Overwrite”?
290023
Acknowledgement that downloading of data
records from the PLC to the operating unit
has started.
–
290024
Acknowledgement that downloading data
records from the PLC to the operating unit
has been completed without any errors.
–
290025
Acknowledgement that downloading of data
records from the PLC to the operating unit
has been terminated due to an error.
Check the configuration:
S
have the tag addresses been set up in
the PLC?
S
does the recipe number exist?
S
does the data record number exist?
S
has the function parameters “Overwrite”?
290026
An attempt has been made to read/write a
data record although the data mailbox is not
free at present.
This error may occur in the case of recipes
for which downloading with synchronization
has been configured.
Set the data mailbox status to zero.
290027
No connection to the PLC can be
established at present. Therefore, the data
record can neither be read nor written.
Possible cause:
No physical connection to the PLC (no cable
plugged in, cable is defect) or the PLC is
switched off.
Check the connection to the PLC.
290030
This message is issued after reselecting a
screen that contains a recipe display in
which a data record has already been
selected.
Reload the data record from the data
medium or retain the current values.
290031
While saving, it was detected that a data
record with the specified number already
exists.
Overwrite the data record or cancel the
process.
290032
While exporting data records, it was detected
that file with the specified name already
exists.
Overwrite the file cancel the process.
290033
Confirmation request before deleting data
records.
–
290041
A data record or file cannot be saved
because the data medium is full.
Delete files no longer required.
Содержание SIMATIC HMI TP 170A
Страница 8: ...Preface vi TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 16: ...Functionality 2 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 24: ...Commissioning 3 8 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 52: ...Installation 7 10 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 62: ...APPENDICES J 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 68: ...Technical Data A 6 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 90: ...System Messages C 20 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...