System Messages
C-6
TP 170A Equipment Manual
Release 12/99
Remedy
Effect/Cause
Number
80024
The function
Copy_Archive is configured not
to permit copying when the target archive
already contains data (Parameter:
Write
mode).
The archive is not copied.
Modify the function
Copy_Archive in the
project, if necessary.
Before initiating the function, delete the target
archive.
80025
The copy action is interrupted.
Data written up to this point is retained.
Deletion of the target table (if configured) is
not executed.
The cancellation is documented by an error
entry
$RT_ERR$ at the end of the target
table.
–
110000
The operating mode status has been
changed. The operating mode is now
offline.
–
110001
The operating mode status has been
changed. The operating mode is now
online.
–
110002
The operating mode status has not been
changed.
Check the connection to the PLCs.
Check whether the address area for the area
pointer “Coordination” in the PLC is
available.
110003
The operating status of the PLC specified is
changed by the function
PLC_Connect_Isolate.
The operating mode is now
offline.
–
110004
The operating status of the PLC specified is
changed by the function
PLC_Connect_Isolate.
The operating mode is now
online.
–
110005
An attempt was made to use the function
PLC_Connect_Isolate to switch the specified
PLC to operating mode
online although the
entire system is in operating mode
offline.
This switch-over is not permissible.
The PLC remains in operating mode
offline.
Switch the complete system to operating
mode
online and execute the function again.
120000
The trend is not displayed because an
incorrect axis to the trend, or incorrect trend,
has been configured.
Change the configuration.
120001
The trend is not displayed because an
incorrect axis to the trend, or incorrect trend,
has been configured.
Change the configuration.
120002
The trend is not displayed because the tag
assigned tries to access an invalid PLC
address.
Check whether the data area for the tag
exists in the PLC, the configured address is
correct or the value range for the tag is
correct.
130000
The action was not executed.
Close other applications.
Delete files no longer required from the hard
disk.
130001
The action was not executed.
Delete files no longer required from the hard
disk.
Содержание SIMATIC HMI TP 170A
Страница 8: ...Preface vi TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 16: ...Functionality 2 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 24: ...Commissioning 3 8 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 52: ...Installation 7 10 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 62: ...APPENDICES J 2 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 68: ...Technical Data A 6 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...
Страница 90: ...System Messages C 20 TP 170A Equipment Manual Release12 99 CuuDuongThanCong com https fb com tailieudientucntt ...