Siemens Energy & Automation, Inc.
S
olid State Outputs
Rating
NO & NC contacts are rated at 1.0 Amp at 120V AC.
Seven are available for the user
Run #1 & 2 Instant
When controller is operating, the RUN contact is closed.
Contact NO
Run #1 & 2 Delayed
NO contact closes immediately on RUN, but delays 100ms
Contact NO
on dropout.
Fault NO & NC
The FAULT NO contact closes and FAULT NC contact opens
for a shorted thyristor.
Up - To - Voltage
When NO contact closes, motor is running at 95% to 100%
of line voltage (after starting is completed).
Electrical Data
Operational Current
Power Dissipation
Surge Capacity
I
2
t, (1/2 cycle)
Current Limit
Catalog
Rating
@ Rated Current
(1 cycle)
Controller
Dual Element
Number
(Amperes)
(Watts)
(Amps)
(A
2
-sec)
Fuse Rating*
3RW3552...
35
84
2000
15,000
60A - RK1
3RW3554...
57
154
2,250
18,000
100A - RK1
3RW3555...
69
166
4,000
80,000
100A - RK1
3RW3557...
80
192
4,000
80,000
100A - RK1
3RW3558...
105
252
7,850
257,000
150A - RK1
3RW3565...
131
315
7,850
257,000
200A - RK1
3RW3566...
195
468
7,850
234,000
300A - RK1
3RW3567...
248
595
11,000
416,000
400A - RK1
3RW3572...
361
866
15,000
815,000
600A - RK1
3RW3583...
480
1152
29,000
2,600,000
800A - RK1
3RW3584...
720
1728
29,000
2,600,000
1200A - RK1
3RW3586...
960
2304
61,000
15,800,000
1600A - RK1
* Fuse rating should not exceed 175% of full load motor rating for class RK1 and L fuses for Type 2 protection.
Current Required
(Milliamperes)
Controller
Current Rating
120V AC Control Voltage
(Amperes)
Control
Fans
35, 57
100
N/A
69, 80, 105
100
200
131, 195, 248
100
150
361
100
300
480, 720, 960
100
450
24