SIDOOR functions
3.1 Basic functions
ATD4xxW Door Controller for Industrial Applications
50
System Manual, 01/2017, A5E38080677-AB
Connection and parameter assignment
The DCOPS signal can be connected to SIDOOR ATD4xxW controllers via "Input 1" of the
terminal X6. See also Section Digital input signals (Page 108).
The connected signal must be activated via the SIDOOR Service Tool (
Main menu >
General setup > Special parameters > Input 1
).
Note
The type 2 ESPE, pressure-sensitive edge and DCOPS functions cannot be implemented
simultaneously.
SIDOOR ATD410W/ATD420W/ATD430W
The DCOPS signal can be sent as shown in Figure 4-5 Sensor signals (Page 152), via the
process image (see Table A-17 DCMD expansion bits (Page 288)) and/or via the local
sensor input ("Input 1" via p4600 - see Table 4-33 Other parameters (Page 176)).
Note
•
The status of the sequential control must be considered when using the DCOPS signal
(process image). The process data is only valid in the "S4: Z_ operation" state (see
Figure 4-4 Sequential control state graph (Page 149)).
•
The light barrier and DCOPS functions can be implemented simultaneously by
connecting to a fieldbus system (process image).
•
The DCOPS, type 2 ESPE or pressure-sensitive edge functions cannot be implemented
simultaneously as sensor functions at input 1.
You can find more detailed information on DCOPS in Section Overview (Page 152).