Certification
6.1.7 Other Approvals
6.1.7
Other Approvals
This device meets the requirements of the following additional standards:
•
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
•
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
•
IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Require-
ments
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RX1510 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Test for IEC 61850-3
Test
Description
Test Levels
Severity
Levels
Enclosure Contact
± 8 kV
IEC 61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal ports
± 4 kV @ 2.5 kHz
Note
DC Power Ports
AC Power Ports
IEC 61000-4-4 Burst (Fast Transient)
Earth ground ports
± 4 kV
4
Signal ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
DC Power Ports
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
Signal ports
DC Power Ports
AC Power Ports
IEC 61000-4-6
Induced (Con-
ducted) RFI
Earth ground ports
10 V
3
100 A/m, continuous
1000 A/m for 1 s
Note
IEC 61000-4-8
Magnetic Field
Enclosure Ports
1000 A/m for 1 s
5
50
RUGGEDCOM RX1510
Installation Manual, 12/2019, C79000-G8976-1055-16