Certification
6.2 EMC and Environmental Type Tests
Description
Test Levels
Enclosure Contact
± 8 kV
ESD
Enclosure Air
± 15 kV
Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40 °F), 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
85 °C (185 °F), 16 Hours
IEC 60068-2-30
Humidity (Damp
Heat, Cyclic)
Test Db
95% (non-condensing),
55 °C (131 °F), 6 cycles
IEC 60255-21-1
Vibration
2 g @ 10-150 Hz
Class 2
Shock
30 g @ 11 ms
Class 2
IEC 60255-21-2
Bump
10 g @ 16 ms
Class 1
Long Life (Random Vibration)
IEC 61373
Shock
Category 1 Class B
IEC 60255-21-3
Seismic
Method A
Level 2
MIL-STD-810G
Altitude
12192 m (40000 ft)
@ 40 °C, 90 minutes
52
RUGGEDCOM RX1510
Installation Manual, 12/2019, C79000-G8976-1055-16