Pointek CLS200/300 (Digital) – QUICK START MANUAL
Page EN-5
mm
mm
m
Eng
lis
h
Low level alarm
• mounted through the tank wall at the detection level
Standard configuration with extensions: top mounting
• Designed for top mounting, for high or low level alarm. Suspend the probe vertically so
that it reaches into the process at the desired detection level.
Process Cautions
• The maximum allowable torque on a horizontally installed rod is 15 Nm.
• Keep unit out of path of falling material, or protect probe from falling material.
• Avoid areas where material build up occurs.
• Take into account material surface configuration when installing unit.
• Ensure tensile load does not exceed probe or vessel ratings.
Mounting Instructions
Pointek CLS200/300 is available in three thread types: NPT or BSPT (R) or BSPP (G)
1
. Make
sure the mounting connection threads are of the same type, then simply screw Pointek
CLS200/300 into the process connection, and hand tighten.
Wiring: standalone unit
Electrical Connection
1.
A
sanitary connection is also available.
WARNING:
• Observe the specifications of the examination certificate valid in your country.
• Observe the laws and regulations valid in your country for electrical installations in
potentially explosive atmospheres.
• Ensure that the available power supply complies with the power supply specified on
the product nameplate and specified in the examination certificate valid in your
country.
• Dust-proof protection caps in the cable inlets must be replaced by suitable screw-
type glands or dummy plugs, which are appropriately certified for transmitters with
explosion-proof protection.
• The lid must not be opened in wet locations while the unit is powered. (A wet
location is location where water or another conductive fluid may be present and is
likely to increase the risk of electric shock.)
• For CE installations use a cable with a braided metallic shield (or armoured cable
where applicable).
50 mm
(2") min
Содержание Pointek CLS200
Страница 1: ...Capacitance Switches Quick Start Manual 09 2010 Pointek CLS200 CLS300 Digital ...
Страница 19: ...Page EN 18 Pointek CLS200 300 Digital QUICK START MANUAL 7ML19985XA82 mmmmm English Notes ...
Страница 37: ...Side DA 18 Pointek CLS200 300 Digital KVIKSTART MANUAL 7ML19985XA82 mmmmm Dansk Notater ...
Страница 55: ...Seite DE 18 Pointek CLS200 300 Digital KURZANLEITUNG 7ML19985XA82 mmmmm Deutsch Notizen ...
Страница 64: ...Σελίδα EL 9 Pointek CLS200 300 Ψηφιακό ΠΕΡΙΛΗΠΤΙΚΟ ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ 7ML19985XA02 Appendix C menu chart ...
Страница 73: ...Σελίδα EL 18 Pointek CLS200 300 Ψηφιακό ΠΕΡΙΛΗΠΤΙΚΟ ΕΓΧΕΙΡΙΔΙΟ ΟΔΗΓΙΩΝ 7ML19985XA82 mmmmm Ελληνικά Σημειώσεις ...
Страница 91: ...Página ES 18 Pointek CLS200 300 Digital MANUAL DE INICIO RÁPIDO7ML19985XA82 mmmmm Español Notas ...
Страница 109: ...Page FR 18 Pointek CLS200 300 numérique MISE EN SERVICE RAPIDE 7ML19985XA82 mmmmm Français Notes ...
Страница 127: ...Pagina IT 18 Pointek CLS200 300 Digitale MANUALE DI AVVIO RAPIDO 7ML19985XA82 mmmmm Italiano Annotazioni ...
Страница 145: ...Pagina NL 18 Pointek CLS200 300 digital QUICK START HANDLEIDING 7ML19985XA82 mmmmm Nederlands Notes ...
Страница 163: ...Página PT 18 Pointek CLS200 300 Digital MANUAL DE INÍCIO RÁPIDO 7ML19985XA82 mmmmm Português Observações ...
Страница 181: ...Sivu FI 18 Pointek CLS200 300 Digitaalinen PIKAKÄYTTÖOPAS 7ML19985XA82 mmmmm Suomi Huomautukset ...
Страница 199: ...Sida SV 18 Pointek CLS200 300 Digital SNABBSTARTSMANUAL 7ML19985XA82 mmmmm Svenska Anmärkningar ...