User Manual OCI600
74 319 0002 0 c
HVAC Products
Communication and delivery of alarms
15.07.2005
You can also test the alarms now, as described in “5.4.1.1
Testing the alarms“.
Note that in case of a modem connection, the line must be
free to be able to receive a call from the OCI600. This means
that you need to close the connection you opened for setting
the parameters.
5.4.3 Sending alarms to SMS receivers
Make the following settings on operating page “Phone num-
ber“ of
ACS Service – [Popcard]
:
Data point
Setting
Phone number
OCI600
Plant phone number of OCI600
is also given in SMS
1)
(entry optional)
Phone number n
Phone number of SMS telephone
provider
Extra number for
mobile phone or
pager n
Number of SMS receiver (mobile phone)
that shall receive the message
2)
Type of alarm re-
ceiver under pho-
ne number n
•
Mobile phone SMS (UCP)
•
Alphanumeric pager, 40 characters
(8N1) (TAP for SMS)
3)
•
Alphanumeric pager, 40 characters
With modem:
Either
parameterization
or sending alarms
Procedure