26/72
Building Technologies
User Manual OCI600
74 319 0002 0 c
HVAC Products
Local setting up
15.07.2005
3.3 Setting up the individual bus
users
3.3.1 Setting up the controllers
3.3.1.1 General
remark
Each controller is given an unambiguous identification in the
form of the segment and the device number, because every
address in an LPB system may only be assigned
once
.
The addressing guidelines are described in Data Sheet
N2030 (Basic System Data).
3.3.1.2
Operating steps on the controllers
1. Turn off the controller’s power supply.
2. Remove the controller’s LPB connection.
3. Apply power again. Do not yet connect the LPB.
4. Address the controller on operating lines
Segment
number
and
Device number
.
Type of
controller
Operating line
for segment
number
Operating line
for device
number
RVP3..., RVL4...
170
169
RWI65.01 79
78
RWI65.02 68
69
RVD2... 132
131
RVP5... 851
850
RVA... 851 850
5. For all controllers, set parameter
Bus power supply
on
the relevant operating line to “Off”
Type of
controller
Operating line for bus power
supply
RVP3.../RVL4... 179
RWI65.01 83
RWI65.02 72
RVD2...
134
RVP5...
852
RVA...
852
Addressing
guidelines