37/72
Building Technologies
User Manual OCI600
74 319 0002 0 c
HVAC Products
Setting up the OCI600 with the ACS7.. software
15.07.2005
2. From
the
Applications > Popcard…
menu, select op-
erating page “Temp module n“. Then, the right half of
the screen will show you the 2 data points “Temp mod-
ule n name“ and “Temp module n address“ for each
temperature module.
3. Double-click on the respective line to open the entry field
for entering the temperature module’s name (maximum
16 characters) and address. The temperature module’s
address must agree with that set on the QAB30.600.
4. Likewise, on the lower operating page “Input n“, you can
enter data points “Temp module n input n name“, “Temp
module n input n minimum“ and “Temp module n input n
maximum“ for each input. The difference of the limit val-
ues must be a minimum of 3 °C.
On line “Temp module n input n measured value“, you
can read the current temperature.
5. Repeat steps 2 to 4 above for the second temperature
module.