32/72
Building Technologies
User Manual OCI600
74 319 0002 0 c
HVAC Products
Setting up the OCI600 with the ACS7.. software
15.07.2005
4 Setting up the OCI600 with
the ACS7.. software
4.1 Opening the connection and
starting up the software
4.1.1 Preparatory
work
1. Connect the PC to the OCI600 using a direct cable link
as described in section “5.2 Communication via RS-
232“.
2. On the OCI600, make the following selection on line
number 08 of operating card 3:
4 = 9600 Baud for a direct connection via RS-232.
3. Make the following selection on line number 11 of operat-
ing card 3:
3 = PC local with alarms
4.1.2 Prerequisite
For setting up the OCI600, the user must have logged in on
user level “Service“ or “Administrator“. For additional infor-
mation, refer to Online Help of your ACS7... software, menu
item
Extras > Password…
4.1.3 Starting up the ACS7..
1. Start
up
ACS Service
via the
ACS Service
icon on your
desktop or via
Start > Programs > ACS > ACS Ser-
vice.
2. Log on using the service or administrator password.
3. Select
Plant > New > Plant…
.
4. The “Save as...“ dialog opens.
Enter a file name for your plant, e.g. “Oslo East“.
5. Confirm by choosing
Save
: The “General” dialog opens.
6. Choose
Next >
: The “Communication” dialog opens.
7. Select the type of central unit:
OCI600
.
Содержание OCI600
Страница 2: ...2 72 Building Technologies User Manual OCI600 74 319 0002 0 c HVAC Products 15 07 2005 ...
Страница 6: ...6 72 Building Technologies User Manual OCI600 74 319 0002 0 c HVAC Products Contents 15 07 2005 ...
Страница 71: ...71 72 Building Technologies User Manual OCI600 74 319 0002 0 c HVAC Products 15 07 2005 ...