8/72
Building Technologies
User Manual OCI600
74 319 0002 0 c
HVAC Products
Overview
15.07.2005
1.3 Internal inputs / outputs and
connection choices (LPB)
Internally, the OCI600 central communication unit has:
•
4 digital inputs
•
2 digital outputs
The following types of devices can be connected via LPB:
•
Maximum 16 LPB controllers (refer to section “1.2
Device combinations“)
•
Maximum 4 Batibus modules each with 4 digital inputs
•
Maximum 4 Batibus modules each with 4 digital outputs
•
Maximum 6 pulse adapters type AEW2.1
•
Maximum 2 temperature measuring units type
QAB30.600 each with 2 inputs
1.4 Functions
The OCI600 central communication unit:
•
Facilitates direct access to LPB controllers with the help
of an operator station (PC) connected either directly or
via modem and on which the ACS7.. software is in-
stalled
•
Monitors all connected devices / modules and its own
inputs and outputs
•
Signals faults to a PC either directly or via modem
•
Signals faults via modem to SMS receivers, fax ma-
chines, pagers, serial printers and Minitel (France only)