2-14
Installation
2. Set the CMI-300 network address by
using the dipswitch settings on switch
SW1. Use Table 16 at the end of this
chapter to set the network address.
Plug the CMI-300 module in the MOM-2/4
card cage and connect the wiring as shown
in the CMI-300 Installation Instructions, P/N
315-091259. Eliminate all troubles from
each module prior to installing the next one.
Installing CRM-4 and CZM-4 Modules
Set the address of each module. Refer to
the CSG-M printout of the final configura-
tion for each module address setting. Refer
to the installation instructions for each
module to set the address dipswitch.
Install the optional modules one at a time
by inserting them in the appropriate card
guides on the MOM-2/4. Eliminate all
troubles from each module prior to install-
ing the next one.
Installing the NIM-1W Network Interface
Module
The NIM-1W installs into the MOM-2/4 card
cage where it occupies one full width slot.
The wiring is connected to TB4 of the
MOM-2 or TB3 of the MOM-4.
The NIM-1W has two configuration
dipswitches. Set the dipswitches before
installing the NIM-1W into the MOM-2/4.
Use switch SW1 to set the MXL-IQ network
address. Set this switch according to the
address where the NIM-1W is installed in
the MXL-IQ’s network map. Refer to the
CSG-M configuration printout for the
address of the module. See Table 16 at the
end of this chapter for settings.
Use switch SW2 to set either the panel
number for networked systems or to select
FSI or Air Sampling operation. Refer to
Table 9 for panel settings, Table 10 for FSI
settings, or Table 11 for Air Sampling
settings.
1. When installing the NIM-1W in a
networked system, set the panel number
to agree with the panel number for the
NIM-1W assigned to the MXL-IQ System
in CSG-M.
2. Switch position 8 selects Style 4 or 7
operation for the NIM-1W network.
3. When installing the NIM-1W for FSI
operation, set the switch to all open (or
OFF).
0
1
E
L
B
A
T
g
n
i
m
m
a
r
g
o
r
P
I
S
F
R
D
D
A
1
2
3
4
5
6
7
8
0
0
0
O
O
O
O
O
O
O
O
F
F
O
r
o
n
e
p
O
=
O
4. When installing the NIM-1W for Air
Sampling connection, set the switch as
follows:
1
1
E
L
B
A
T
g
n
i
m
m
a
r
g
o
r
P
g
n
il
p
m
a
S
ri
A
R
D
D
A
1
2
3
4
5
6
7
8
g
n
il
p
m
a
S
ri
A
O
O
O
O
O
O
O
X
F
F
O
r
o
n
e
p
O
=
O
N
O
r
o
d
e
s
o
l
C
=
X
After setting the switches, install the
NIM-1W into the MOM-2/4 card cage.
Make sure that the module is in the card
guides and the card edge is firmly seated in
the connectors on the MOM-2/4.
Installing the CSM-4 Signal Module
Before installing the CSM-4 in the
MOM-2/4, you must set the network
address, configure each circuit according to
the CSG-M program [as Local (NACs),
Municipal Tie, Leased Line, or Releasing
Service], and set the default modes (trouble
and alarm) as follows. Refer to Table 12 for
the Modes of Operation.
a. Set the Network Address
The network address is set on dipswitch S1
(See Figure 12, page 1-8). See the CSG-M
printout for the proper address. Use Table
16 at the end of this chapter to set the
switches.
Содержание MXL-IQ
Страница 50: ...2 20 Installation ...
Страница 126: ...A 2 Appendix A ...
Страница 128: ...B 2 Appendix B ...
Страница 138: ...F 4 Appendix F ...
Страница 140: ...G 2 Appendix G ...
Страница 142: ...H 2 Appendix H ...
Страница 154: ...K 2 Appendix K ...
Страница 162: ...L 8 Appendix L ...
Страница 166: ...M 4 Appendix M ...
Страница 168: ...N 2 Appendix N ...
Страница 178: ...Index 6 Index ...