E-2
Appendix E
With Device Confirmation, the B
C
verification time known as System Justi-
fied Alarm time is also adjustable. It is the
same time used by both ionization and
photo detectors. If a device is individually
selected for alarm verification, the alarm
verification feature takes priority over the
device confirmation option. For adjustment
ranges, refer to the CSG-M Programming
Manual, P/N 315-090381.
There is an Override menu selection in the
Test menu of MXL-IQ. Select Alr_Verify to
disable all alarm verification or select
Alr_Confirm to disable all alarm confirma-
tion for a period of up to 4 hours or until
manually re-enabled.
Содержание MXL-IQ
Страница 50: ...2 20 Installation ...
Страница 126: ...A 2 Appendix A ...
Страница 128: ...B 2 Appendix B ...
Страница 138: ...F 4 Appendix F ...
Страница 140: ...G 2 Appendix G ...
Страница 142: ...H 2 Appendix H ...
Страница 154: ...K 2 Appendix K ...
Страница 162: ...L 8 Appendix L ...
Страница 166: ...M 4 Appendix M ...
Страница 168: ...N 2 Appendix N ...
Страница 178: ...Index 6 Index ...