J-7
Appendix J
Trouble Message
The Probable Cause Is:
Signal Mod A/D Convert Fail
The CSM-4 at this address has a failed
analog-to-digital converter.
Signal Module Zone Code
Zone code failure on the CSM-4 module.
Software Key Violation
Incorrect Software Key Installed (NCC
only).
Stack Fault Call Support
When the message
Call Support
appears,
a four letter Alpha ID will be displayed. This
number is necessary when reporting the
problem to Siemens Industry, Inc.
Style 4 Network Mode
The Style 4 jumper on a NET-7 is found on
a Style 7 system. Move the jumper to the
Style 7 position.
Style 7 Network Mode
The Style 7 jumper on a NET-7 is found in
the Style 4 mode. Move the Style 7 jumper
to the Style 4 position.
System Commissioning Mode
The system has been put in the commis-
sioning mode.
System Signal Power Failure
A CSM-4 has lost power to its output
circuits.
Tamper Switch
This is a security-type message for the
tamper switch on the SMB-2 board when
the system is selected for UL 1076 operation.
Too Many ALD-2s
To many ALD-2Is are installed on the system.
This is beyond the maximum allowed.
Trouble Causing Input
A device programmed on the system as
trouble causing
has been activated and has
changed state.
Trouble Type Not Defined
Unspecified trouble has been received from
this address.
Troubles Summarized
While the system is in the commissioning
mode, the modules will display this message
in lieu of all the devices on this module.
Unspecified Dev Responding
An analog device has reported at an
address not assigned in CSG-M.
Содержание MXL-IQ
Страница 50: ...2 20 Installation ...
Страница 126: ...A 2 Appendix A ...
Страница 128: ...B 2 Appendix B ...
Страница 138: ...F 4 Appendix F ...
Страница 140: ...G 2 Appendix G ...
Страница 142: ...H 2 Appendix H ...
Страница 154: ...K 2 Appendix K ...
Страница 162: ...L 8 Appendix L ...
Страница 166: ...M 4 Appendix M ...
Страница 168: ...N 2 Appendix N ...
Страница 178: ...Index 6 Index ...