J-2
Appendix J
Trouble Message
The Probable Cause Is:
CMI-300 General Trouble
Communications trouble between the CMI-
300 and the CXL. Data is attempting to
transmit.
CSGM Out Of Date
This MXL-IQ (node) will need to be updated
with the latest CSG-M networked program.
A network CSG-M has been loaded on
another MXL-IQ (node) and has a reference
to this MXL-IQ (node).
Daily Detector Test Abnormal
Device is defective.
Detector Trouble
AnaLASER detector in need of repair.
Device Communication Error
An analog device whose response has
failed error checking.
Device Detected Waveform Error
An analog device reports this trouble if it
receives an unknown polling waveform.
Device LED Turned On
A device LED was turned on from the Test
menu of the MXL-IQ.
Device Multiple Response
Two or more analog devices at the same
address have reported during normal
supervision.
Device Out of Calibration
This message is used with XLD and is the
same as the XL-3 message,
Response out of window at cal.
Device Receive Error
An analog device reports this trouble
if it receives an incorrect analog
transmission.
Event log 80% full
Use extract history in CSG-M to reset the
MXL-IQ history log.
Event log 90% full
Use extract history in CSG-M to reset the
MXL-IQ history log.
Function Recursion Trouble
The number of evaluations of output logic
required until outputs are stable has
exceeded the system maximum. Rewrite
CSG-M to simplify functions.
Ground Fault Minus
Low impedance to the negative side of one
of the field wiring circuits to earth ground.
Содержание MXL-IQ
Страница 50: ...2 20 Installation ...
Страница 126: ...A 2 Appendix A ...
Страница 128: ...B 2 Appendix B ...
Страница 138: ...F 4 Appendix F ...
Страница 140: ...G 2 Appendix G ...
Страница 142: ...H 2 Appendix H ...
Страница 154: ...K 2 Appendix K ...
Страница 162: ...L 8 Appendix L ...
Страница 166: ...M 4 Appendix M ...
Страница 168: ...N 2 Appendix N ...
Страница 178: ...Index 6 Index ...