105/116
Smart Infrastructure
Basic Documentation LME7...
CC1P7105en
15 Operation via internal LED
24.07.2020
A
>3 s
Alternately
Press
A
for >3 seconds to display alternately
LoA
and
41
.
The
relative
value
41
of the current position or current
speed is displayed.
Actuator position 0°
0
potentiometer value =
0% display
Actuator position high-fire
>0°
<90° = potentiometer value
>0
<1000
= 100%
display
Current speed
0 rpm = 0
%
display
Current speed corresponds
to the rated load speed =
100% display
The actual value (example
41
%) is displayed and the signal
lamp blinks green.
Example: Position of actuator or the current speed
41
%
(based on range between high-fire and 0° or 0 rpm)
A
and
+
or
-
Press
A
simultaneously with
+
or
-
to adjust the
actuator position or the fan speed between low-fire (x%) and
high-fire (100%).
Release the buttons when the required position or speed is
reached.
Signal lamp blinks s green.
Example: Value
43
Alternately
Display shows alternately
LoA
and
43
.
Signal lamp blinks green.
Example: Required position of actuator or current speed
43
%
-
and
+
Press
-
and
+
simultaneously (Escape) to return to
normal operation.
Display:
oP
When manual adjustment is completed, the actuator or the
PWM fan returns to the analog preset output!