111/116
Smart Infrastructure
Basic Documentation LME7...
CC1P7105en
15 Operation via internal LED
24.07.2020
15.8 Manual
restore
-
and
+
>1 s
Press
-
and
+
simultaneously for >1 second (Escape)
for starting the manual restore process.
Parameter
PrC
appears.
Display:
PrC
-
or
+
Press
-
or
+
for parameter
rSt
.
Display:
rSt
nfo
1…3 s
run
appears during download (restore process) of program
sequence.
Alternately
Display shows alternately
End
and
rSt
.
Display shows the end of data exchange.
Signal lamp blinks red.
After 2 minutes, the LME7 changes to
Loc 138
LC
D
B
ild
0
6
/090
8
Alternately
After the restore process, the LME7 is automatically in the
lockout position (Loc 138) and must be reset for operation.
nfo
>1 s
LC
D
B
ild
0
2
/090
8
Press
nfo
(for > 1 second) to reset the LME7.
Display