Function
24.07.2020
6 Function
6.1 Preconditions for burner startup
LME7
is
reset
All contacts in the line are closed, there is a request for heat
No
undervoltage
Air pressure switch or POC must be in its no-load position, or Dbr1 is connected to
terminal X2-02 (depending on program sequence)
Flame detector is darkened and there is no extraneous light
All contacts in the safety loop are closed
6.2 Undervoltage
Safety shutdown from the operating position takes place should mains voltage
drop below about AC 75 V (UN = AC 120 V)
Restart is initiated when mains voltage exceeds about AC 100 V (UN = AC 120
V)
Safety shutdown from the operating position takes place should mains voltage
drop below about AC 165 V (UN = AC 230 V)
Restart is initiated when mains voltage exceeds about AC 195 V (UN = AC 230
V)
6.3 Controlled
intermittent
operation
Depending on the PME7, refer to
User Documentation A7105.x
.
After no more than 24 hours of continuous operation, the LME7 initiates an automatic
controlled shutdown followed by a restart.