45/116
Smart Infrastructure
Basic Documentation LME7...
CC1P7105enr
6
Function
24.07.2020
6.6 Restart
limitation
Depending on the PME7, refer to
User Documentation A7105.x
.
6.6.1 Restart in the event of loss of flame
If the flame is lost during operation, a certain number of restarts per controlled startup
can be performed via the control thermostat or pressurestat depending on the
parameter settings in the PME7, otherwise a non-volatile lockout will be initiated. With
restarts from the operating position (loss of flame), the flame must have been
established on completion of the safety time, or else a non-volatile lockout will be
initiated.
6.6.2 Repetition in case of
no flame is established by the end of
safety time (TSA)
If there is
no establishment of flame at the end of the safety time,
a non-volatile lockout
will be initiated.