HMI menu ID Parameter
Description
Default value
[unit]
Value range
Access
level
2.4.2.5.3
Loop current scale
Select current output scaling ac‐
cording to desired measurement
range and fail-safe mode.
● 4 to 20 mA
NAMUR
● 4 to 20 mA
NAMUR
● 4 to 20 mA US
● 4 to 20 mA
(fault = 0 mA)
● 4 to 20 mA
● 0 to 20 mA
User
2.4.2.5.4
Upper range value
Assign process value to the
nominal upper range value
1)
1)
User
2.4.2.5.5
Lower range value
Assign process value to the
nominal lower range value
1)
1)
User
2.4.2.5.6
Damping value
Set filter time constant. Defines
the damping of the current out‐
put signal. 0.0 means filter is off
0 s
● 0 to 100 s
User
2.4.2.5.7
Fail-safe behavior
Select current output reaction in
case of a fault.
Lower fault
current
● Lower fault
current
● Upper fault
current
● Last valid
value
● Current value
● Fail safe value
User
2.4.2.5.8
Fail-safe value
Define fail-safe current output
value if 'Fail-safe behaviour' pa‐
rameter is set to ’Fail-safe value’.
3.5 mA
● 0 to 25 mA
User
2.4.2.5.9
Fail-safe minimum dura‐
tion
Minimum time the output stays
in fail-safe mode. Short events
will be prolonged.
0 s
● 0 to 100 s
user
2.4.2.6
Frequency output
2.4.2.6.1
Process value
Select process value for current
output.
Mass flow
● Mass flow
● Volume flow
● Standard
volume flow
● Density
● Reference
density
● Medium
temperature
● Fraction A
● Fraction B
● Fraction A %
● Fraction B %
User
Default settings
B.5 Inputs and outputs
MASS 2100 & FC300 (FCT030)
294
Operating Instructions, 06/2017, A5E39789040-AA
Содержание FC300
Страница 9: ...Index 515 Table of contents MASS 2100 FC300 FCT030 Operating Instructions 06 2017 A5E39789040 AA 9 ...
Страница 10: ...Table of contents MASS 2100 FC300 FCT030 10 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 36: ...Description 3 7 Theory of operation MASS 2100 FC300 FCT030 36 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 90: ...Connecting 5 4 Device nameplates MASS 2100 FC300 FCT030 90 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 258: ...Dimension drawings 12 4 Mounting bracket MASS 2100 FC300 FCT030 258 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 478: ...Default settings B 15 Language MASS 2100 FC300 FCT030 478 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 518: ...Index MASS 2100 FC300 FCT030 518 Operating Instructions 06 2017 A5E39789040 AA ...