HMI menu ID Parameter
Description
Default value
[unit]
Value range
Access
level
2.4.1.4
Direction
Select measured flow direction.
The flow meter will only output
current when flow value is meas‐
ured in selected direction.
Positive
● Positive
● Negative
● Bidirectional
● Bidirectional
(symmetric)
User
2.4.1.5
Loop current scale
Select current output scaling ac‐
cording to desired measurement
range and fail-safe mode.
● 4 to 20 mA
(3.5) 3.8…
20.5 (22.6)
NAMUR
● 4 to 20 mA
(3.5) 3.8…
20.5 (22.6)
NAMUR
● 4 to 20 mA /
(3.75) 4 to
20.8 (22.6) US
User
2.4.1.6
Upper range value
Assign process value to the up‐
per output current (20mA)
1)
1)
User
2.4.1.7
Lower range value
Assign process value to the low‐
er output current
1)
1)
User
2.4.1.8
Fail safe activation con‐
dition
Fail-safe becomes active if ei‐
ther the selected process value
is unreliable, or the device
shows "Maintenance alarm".
Invalid proces‐
value
● Invalid
process value
● Maintenance
alarm
User
2.4.1.9
Damping value
Set filter time constant. Defines
the damping of the current out‐
put signal.
0 s
0 to 100 s
User
2.4.1.10
Fail-safe behaviour
Select current output reaction in
case of a fault.
Lower fault cur‐
rent
● Lower fault
current
● Upper fault
current
● Last valid
value
● Current value
● Fail safe value
User
2.4.1.11
Fail safe value
Define fail-safe current output
value if 'Fail-safe behaviour' pa‐
rameter is set to ’Fail-safe value’.
3.5 mA
0 to 25 mA
2.4.1.12
Fail-safe minimum dura‐
tion
Minimum time the output stays
in fail-safe mode. Short events
will be prolonged.
0
0 to 100 s
1)
: See Sensor dimension dependent default settings (Page 259)
2)
Process value is set to Mass flow
3)
Process value is set to Volume flow
4)
Process value is set to Density
Default settings
B.5 Inputs and outputs
MASS 2100 & FC300 (FCT030)
292
Operating Instructions, 06/2017, A5E39789040-AA
Содержание FC300
Страница 9: ...Index 515 Table of contents MASS 2100 FC300 FCT030 Operating Instructions 06 2017 A5E39789040 AA 9 ...
Страница 10: ...Table of contents MASS 2100 FC300 FCT030 10 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 36: ...Description 3 7 Theory of operation MASS 2100 FC300 FCT030 36 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 90: ...Connecting 5 4 Device nameplates MASS 2100 FC300 FCT030 90 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 258: ...Dimension drawings 12 4 Mounting bracket MASS 2100 FC300 FCT030 258 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 478: ...Default settings B 15 Language MASS 2100 FC300 FCT030 478 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 518: ...Index MASS 2100 FC300 FCT030 518 Operating Instructions 06 2017 A5E39789040 AA ...