
Positive flow with negative scaling
v
v
mA
kg /h
100 kg/h
400 kg/h
v
v
v
)&
P$
P$
P$
P$
①
Low-flow cut-off
②
Upper scaling
③
Maximum output current
④
Upper alarm current
⑤
Upper range
⑥
Lower scaling
⑦
Lower range
⑧
Minimum output current
⑨
Measurement range
Current output setting
● Process value = Mass flow
● Direction = Symmetric
● Current Mode = 4-20 mA (maximum 25 mA)
● Upper Scaling = 100 kg/h
● Lower Scaling = 400 kg/h
● Fail Safe Mode = Maximum current
● Low-Flow Cut-Off = 25 kg/h
Technical data
11.5 Outputs
MASS 2100 & FC300 (FCT030)
224
Operating Instructions, 06/2017, A5E39789040-AA
Содержание FC300
Страница 9: ...Index 515 Table of contents MASS 2100 FC300 FCT030 Operating Instructions 06 2017 A5E39789040 AA 9 ...
Страница 10: ...Table of contents MASS 2100 FC300 FCT030 10 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 36: ...Description 3 7 Theory of operation MASS 2100 FC300 FCT030 36 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 90: ...Connecting 5 4 Device nameplates MASS 2100 FC300 FCT030 90 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 258: ...Dimension drawings 12 4 Mounting bracket MASS 2100 FC300 FCT030 258 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 478: ...Default settings B 15 Language MASS 2100 FC300 FCT030 478 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 518: ...Index MASS 2100 FC300 FCT030 518 Operating Instructions 06 2017 A5E39789040 AA ...