8.8.4
Fault handling
The transmitter fault handling provides monitoring of both dosing time and amount. The
configuration of the fault handling is done in menu 2.5.4.6 Fault Handling.
Dosing timeout monitoring
The dosing timeout monitoring checks whether the dosing procedure has been finished within
the configured Duration Time (menu item 2.5.5.7.2 for Recipe 1). If the duration time is
exceeded, an alarm will be triggered, see Fault codes and corrective actions (Page 188).
Dosing overrun monitoring
The dosing overrun monitoring checks if the flow amount exceeds the defined Overrun Value
(menu item 2.5.5.7.3 for Recipe 1). If the overrun value is exceeded, an alarm will be triggered,
see Fault codes and corrective actions (Page 188).
This function can detect a valve malfunction (non-closure) caused by a blockage, wear, etc.
8.9
Audit trail logging
The audit trail includes any values or settings changed by users. The audit trail is automatically
stored with information on the change as well as the time (real-time) and by which interface
(display, bus communication or USB) the change was made.
Audit trail information is logged on the SensorFlash card, as a parameter and command
change file which include below informations:
● Timestamp
● MODBUS register
● Previous value
● New value
● Data type
● Interface ID
Example: 2017-06-08 13:48:05;9003;73;74;Uint8;HMI
The transmitter can log up to 100 entries in each of the audit trail log lists:
● "Parameter change log" (menu item 3.9.1)
● "Firmware update change log" (menu item 3.9.3)
Each audit trail list can be cleared by the user.
See also "Diagnostic log" (menu item 3.2.2)
8.10
Diagnostic log
All unacknowledged diagnostic information are listed in the Diagnostic log menu item 3.2.2
Functions
8.10 Diagnostic log
MASS 2100 & FC300 (FCT030)
Operating Instructions, 06/2017, A5E39789040-AA
163
Содержание FC300
Страница 9: ...Index 515 Table of contents MASS 2100 FC300 FCT030 Operating Instructions 06 2017 A5E39789040 AA 9 ...
Страница 10: ...Table of contents MASS 2100 FC300 FCT030 10 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 36: ...Description 3 7 Theory of operation MASS 2100 FC300 FCT030 36 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 90: ...Connecting 5 4 Device nameplates MASS 2100 FC300 FCT030 90 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 258: ...Dimension drawings 12 4 Mounting bracket MASS 2100 FC300 FCT030 258 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 478: ...Default settings B 15 Language MASS 2100 FC300 FCT030 478 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 518: ...Index MASS 2100 FC300 FCT030 518 Operating Instructions 06 2017 A5E39789040 AA ...