Operating Manual of FC18 Controller
Page: 59/70
APPENDIX 1 PARAMETER LIST
Equipment type
Editable item
Parameter description
System
Text
System name
Station
-
FC1820
-
FC1840
-
FC186X
Text
Controller name
Login time
Under 2nd/3rd level, if there is no operation in preset login time, controller
will automatically log out to 1
st
level. Effective value: 1-60 minutes.
Walk-test time
When controller is being tested, it will automatically resume to normal status
after preset walk-test time, without the need of manual operation. Effective
value: 1-60 minutes.
Sound level
Setup sound volume of beeper, with effective value of 0-7.When the value is
0, it is silence mode.
LCD closing time If there is no operation of controller in preset LCD off time, LCD will shut off
back light. Effective value: 1-60 minutes.
Main board input/output
Text
Main board input/output (default)
P2 line
Text
P 2 line#
Topology type
Option 1: Stub
Option 2: Loop (default)
Power supply
Text
Power supply (default)
Interlocking panel
Text
Interlocking panel (default)
FDO181 smoke detector
Text
Device location description
Sensitivity
Option 1: Standard (default)
Option 2: Sensitive
FDO181 heat detector
Text
Device location description
Detection mode
Option 1: A2S (default)
Option 2: A2R
FDM181 manual call point
Text
Device location description
FDCI181 input module
Text
Device location/function description
FDCIO181 input/output
module
Text
Device location/function description
Supervision input
(FDCI181&FDCIO181)
Text
Device location/function description
Inversion
Option 1: Normal (Active When NO is closed) (default)
Option 2: Inverting (Active when NC is open)
Supervision input
(interlocking panel and main
board input)
Text
Device location/function description
Status input
(FDCI181&FDCIO181)
Text
Device location/function description
Status input
(interlocking panel and main
board input)
Text
Device location/function description
Alarm input
(FDCI181&FDCIO181)
Text
Device location/function description