Operating Manual of FC18 Controller
Page: 12/70
Fig. 2-10 Interlocking panel connection diagram (the same for other channels)
Note: the load range of each output is 24VDC, 600
Ω
– 1.2k
Ω
3.
DIP-SWITCH
There is a 8-digit Dip-switch FCnet ID (Fig. 2-2) on main unit. The 1-6 digit of Dip-switch is available, used to set 1-32
address of main unit. The 7-8 digit must be “Off”.
Table 2-4
FCnet
Address
Dip-Switch
Reserved
1
2
3
4
5
6
7
8
Null
Off
Off
Off
Off
Off
Off
Off
Off
1
On
Off
Off
Off
Off
Off
Off
Off
2
Off
On
Off
Off
Off
Off
Off
Off
3
On
On
Off
Off
Off
Off
Off
Off
4
Off
Off
On
Off
Off
Off
Off
Off
5
On
Off
On
Off
Off
Off
Off
Off
31
On
On
On
On
On
Off
Off
Off
32
Off
Off
Off
Off
Off
On
Off
Off
There is a 8-digit Dip-switch Int. ID (Fig. 2-2) on interlocking panel .The 1-4 digit of Dip-switch is available, used to set
address of interlocking panel. The address No. is fixed as 15. The 5-8 digit is “Off”.
Table 2-5
Address
D1
D2
D3
D4
D5
D6
D7
D8
15
On
On
On
On
Off
Off
Off
Off
There is a 2-digit Dip-switch CAN End (Fig. 2-2) on main unit. It is used to set 120
Ω
EOL resistor of FC18-BUS and
FR18-BUS.
Table 2-6
1
On
:
FC18-BUS EOL is connected
;
Off
:
not connected
2
On
:
FR18-BUS EOL is connected
;
Off
:
not connected